background image

 

DGP-848 Control Panel

 

13

Figure 15: Delayed 24-hr. Fire Zone

4.2.8 Standard 24Hr Fire Zone

S

ECTIONS

 [101] 

TO

 [148]: F

IRST

 

DIGIT

 = A

For details how to connect smoke detectors to the control panel, 
refer to Fire Circuits in section 2.15 on page 7. When a zone is 
programmed as a Fire zone, the zone becomes normally open and 
requires an EOL resistor. The zone will not function as normally 
closed. Whenever a Standard 24Hr Fire Zone is triggered, whether 
it is armed or disarmed, the control panel can:

send a Zone Alarm report code (see section 8.2.5 on page 
25).

send a Fire Loop Trouble Report (see section 8.2.11 on page 
26) if 
a tamper/wiring fault occurs on a Fire Zone. A “Zone 
Fault Trouble” will also appear in the keypad's Trouble Display.

generate a Fire alarm, which is always audible, regardless of 
other settings. Fire alarms will generate an intermittent bell/
siren output signal as demonstrated in Figure 16.

Figure 16: Bell/Siren Output During Fire Alarm

4.2.9 Stay Delay Zone

S

ECTIONS

 [101] 

TO

 [148]: F

IRST

 

DIGIT

 = B 

TO

 E

When a Stay Delay zone is armed using the Regular or Force 
arming methods, the control panel will process the zone as an 
Instant zone (see section 4.2.4 on page 12). When a Stay Delay 
zone is armed using the Stay or Instant arming methods and the 
zone is triggered, the control panel will not generate an alarm until 
the programmed Stay Delay has elapsed. A zone can be defined 
with one of four Stay Delays. Each Stay Delay is associated with an 
Entry Delay Timer. To program the Entry Delay Timer, key in the 
desired 3-digit delay value (000 to 255 seconds) into the 
corresponding section:

Stay Delay 1 = Entry Delay 1 Timer in section [230]
Stay Delay 2 = Entry Delay 2 Timer in section [231]
Stay Delay 3 = Entry Delay 3 Timer in section [232]
Stay Delay 4 = Entry Delay 4 Timer in section [233]

Please note that the Entry Delay Timers are the same 
timers used for Entry Delay zones. 

4.3 Zone Partition Assignment

S

ECTIONS

 [101] 

TO

 [148]: S

ECOND

 

DIGIT

 = 1 

TO

 4

The control panel provides the option of partitioning the security 
system into two, three, or four completely independent systems. 
Therefore, each zone must be assigned to one partition as 
described in Figure 13 on page 11. For more information on 
Partitioning, refer to section 12.5 on page 36

4.4 Zone Options

Each zone can be programmed with one or more of the options 
described below. Program the zone options as described in Figure 
13 on page 11
.

4.4.1 Auto Zone Shutdown

S

ECTIONS

 [101] 

TO

 [148]: O

PTION

 [1]

When option [1] is disabled and an armed zone is breached, the 
control panel generates an alarm: it may send an alarm report (see 
section 8.11 on page 28), 
activate the bell output, etc. If the same 
zone re-opens during the same alarm, another alarm report may be 
sent, the bell output may re-activate and so on. When option [1] is 
enabled on a zone, the control panel will stop generating an alarm 
when the Auto Zone Shutdown Limit is reached during one armed 
period. The control panel will ignore zones with the Auto Zone 
Shutdown option that have surpassed the programmed limit. To 
program the Auto Zone Shutdown Limit, key in the desired 3-digit 
counter (000 to 015) into section [217]. Entering 000 disables this 
feature. The Auto Zone Shutdown Limit resets every time the 
partition that is assigned to the corresponding zone is armed.

Delayed Fire Zone

Triggered

Activate bell/siren output & delay

report transmission for 30 seconds.

Yes

Yes

Any key on

keypad pressed

within 30

seconds?

Bell/siren silenced. Delay report

transmission an additional 90 sec.

Problem

corrected?

Latch alarm and transmit
report code as described

in the section "Standard

24Hr. Fire Zone".

END

Alarm Disabled

No

Has a 2nd

Delayed Fire

Zone opened in

30 sec.?

No

Yes

Yes

No

Has the zone

closed within
30 seconds?

Yes

No

Summary of Contents for Digiplex DGP-848

Page 1: ...Digiplex Control Panel DGP 848 V4 1 Reference and Installation Manual Includes DGP2 641BL RB Installation Instructions DGP 848...

Page 2: ......

Page 3: ...ch Features 20 Exit Delay 20 Keypad Lock out Feature 20 Maximum Bypass Entries 21 Display Bypass If Armed 21 Bell Squawk 21 Ring back 21 Switch To Stay Arming 21 Always Force Arm When Regular Arming 2...

Page 4: ...Access Levels 42 Schedules 42 Holiday Programming 42 Logging Access Control Events 42 Global Access Door Features 43 WinLoad Software 44 Answering Machine Override 44 Ring Counter 44 Panel Identifier...

Page 5: ...ne combus for up to 95 modules All modules have Plug and Play capability Connect modules up to 3000ft 914m from the panel Full supervision and sabotage proof technology without additional wiring Up to...

Page 6: ...nds If the battery is disconnected if its capacity is too low or if the battery voltage drops to 10 5 volts or less when there is no AC the Battery Trouble message will appear in the Trouble Display A...

Page 7: ...To metallic enclosure To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals COMBUS AUX POWER Refer to transformer req...

Page 8: ...ontact Modules DGP2 ZC1 _______ X 30mA __________ mA 1 Zone Expansion Modules DGP2 ZX1 _______ X 30mA __________ mA 4 Zone Expansion Modules APR3 ZX4 _______ X 30mA __________ mA 8 Zone Expansion Modu...

Page 9: ...0ft Magellan Module MG RCV3 A 35mA LCD Keypad DGP2 641BL D 110mA 15m 50ft 7 5m 25ft 7 5m 25ft 15m 50ft Motion Detector Module DGP2 70 E 30mA LED Keypad DGP2 648 F 110 mA LED Keypad DGP2 648 G 110 mA A...

Page 10: ...would exceed the system s capacity For information on how to assign a detection device to a zone in the control panel please refer to Zone Programming on page 11 Before connecting a module to the cont...

Page 11: ...shown in Figure 3 on page 3 2 14 Keyswitch Connections Connect the keyswitches to the keypad control panel or Zone Expansion Module s hardwired input terminals as shown in Figure 9 Once a keyswitch i...

Page 12: ...elay will cause the control panel to transmit the Fire Loop Trouble report if programmed in section 707 To reset unlatch the smoke detector after an alarm verify that the negative of the smoke detecto...

Page 13: ...the right action key Exit on Grafica keypads as many times as needed to return to the desired screen Please note that a module s serial number can be located on the module s PC board or it may already...

Page 14: ...that the write protect jumper is on 3 Enter section 965 to copy the contents of the panel except sections 001 to 048 device serial numbers and 049 to 056 keyswitch serial numbers to the key 966 to co...

Page 15: ...esent zones 1 to 48 respectively Zone Parameters Sections 101 to 148 represent zones 1 to 48 respectively Enter the 8 digit SERIAL NUMBER of the addressable detection device or module that has a hardw...

Page 16: ...ry Delay 1 Timer 230 Entry Delay 2 Timer 231 Entry Delay 3 Timer 232 Entry Delay 4 Timer 233 Please note these are the same timers used for Stay Delay zones see section 4 2 9 on page 13 Entry Delay zo...

Page 17: ...lay 4 Timer in section 233 Please note that the Entry Delay Timers are the same timers used for Entry Delay zones 4 3 Zone Partition Assignment SECTIONS 101 TO 148 SECOND DIGIT 1 TO 4 The control pane...

Page 18: ...digit delay value 010 to 255 seconds into section 200 Fire Zones cannot be set as Intellizones 4 4 7 Delay Alarm Transmission SECTIONS 101 TO 148 OPTION 8 When an alarm condition occurs on a zone wit...

Page 19: ...Panel 15 Table 5 Hebrew Keypad Letter Assignment Table 6 Russian Keypad Letter Assignment Table 7 Special Characters Catalogue Table 8 Hebrew Special Characters Catalogue Table 9 Russian Special Chara...

Page 20: ...t 004 speed 205 Panel Terminal 5 Input 005 speed 206 Panel Terminal 6 Input 006 speed 207 Panel Terminal 7 Input 007 speed 208 Panel Terminal 8 Input 008 speed 209 Panel Doubler 1 Input 009 speed 210...

Reviews: