background image

6

 

Reference & Installation Manual

2.9 Programmable Outputs

The Digiplex control panel comes standard with PGM1 and PGM2. 
PGM3 to PGM5 are optional. When a specific event or condition 
occurs in the system, a PGM can be programmed to reset smoke 
detectors, activate strobe lights, open/close garage doors and much 
more. For details on how to program the PGMs, refer to section 10 
on page 30. 

PGM1 provides a maximum 100mA output, PGM2 to PGM4 
provide a maximum 50mA output and PGM5 is a relay output that 
provides a maximum of 5A. If the current draw on the PGM is to 
exceed the current output, we recommend the use of a relay as 
shown in Figure 6. PGM1 to PGM4 are normally open outputs and 
PGM5 is a normally open or normally closed 5A relay. Also, note 
that PGM1 can be programmed as a 2-wire smoke detector input. 
For more information, refer to section 2.15.1 on page 7 and section 
10.4 on page 31 of th
is manual.

Figure 6: PGM Relay Output

2.10 Combus Connections

The combus is a 4-wire combus that provides power and two-way 
communication between the control panel and all modules 
connected to it. All addressable detection devices, keypads and 
Digiplex modules are connected to the combus, which can support 
up to 95 modules. Connect the four terminals labeled RED, BLK, 
GRN and YEL of each detector, keypad or module to the 
corresponding terminals of the control panel as shown in Figure 3 
on page 3
. Please note that all modules can be connected in a star 
and/or daisy chain configuration. The final device on the combus 
should not be more than 914m (3000ft) from the control panel. The 
total run of every wire in the system must not exceed 914m 
(3000ft). For example, if 10 runs of wire are each 305m (1000ft), 
the total would exceed the system’s capacity. For information on 
how to assign a detection device to a zone in the control panel, 
please refer to Zone Programming on page 11.

Before connecting a module to the control panel, 
shutdown the control panel by removing AC and 
battery power.

2.10.1 Connecting the Combus in Noisy Environments

When installing the combus wires in proximity to high electrical 
interference such as neon lights, motors, high-voltage wiring, 
transformers, or when connecting the combus across separate 
buildings, you must use shielded cables. Connect the shielded 
cable as detailed below:

Within the Same Building: Strip the outer jacket at one end of the 
shielded cable to expose the shield and connect the shield to the 
control panel ground (not the dialer ground), while leaving the 
shield at the other end of the cable open (floating).

Across Separate Buildings: Strip the outer jacket at one end of 
the shielded cable to expose the shield. In the same building that 

houses the control panel, connect the exposed shield to a cold 
water pipe or any other earth ground available, while leaving the 
shield at the other end of the cable open (floating). The same 
configuration applies for any subsequent building.

2.11 Single Zone Connections

In addition to the combus, the Digiplex control panel includes eight 
hardwired input terminals for use with traditional hardwired door 
contacts, smoke detectors and/or motion detectors. One to eight-Zone 
Expansion Modules that connect to the combus are also available. 
Devices connected to hardwired input terminals must be assigned to a 
zone and the zone's parameters must be defined. Please refer to 
Zone Programming on page 11. for morinformation. Figure 7 
demonstrates single zone (ATZ disabled) hardwire input terminal 
connections recognized by the Digiplex system. For UL listed 
installations, use EOL resistor part #2011002000.

Figure 7: Single Zone Input Connections

Summary of Contents for Digiplex DGP-848

Page 1: ...Digiplex Control Panel DGP 848 V4 1 Reference and Installation Manual Includes DGP2 641BL RB Installation Instructions DGP 848...

Page 2: ......

Page 3: ...ch Features 20 Exit Delay 20 Keypad Lock out Feature 20 Maximum Bypass Entries 21 Display Bypass If Armed 21 Bell Squawk 21 Ring back 21 Switch To Stay Arming 21 Always Force Arm When Regular Arming 2...

Page 4: ...Access Levels 42 Schedules 42 Holiday Programming 42 Logging Access Control Events 42 Global Access Door Features 43 WinLoad Software 44 Answering Machine Override 44 Ring Counter 44 Panel Identifier...

Page 5: ...ne combus for up to 95 modules All modules have Plug and Play capability Connect modules up to 3000ft 914m from the panel Full supervision and sabotage proof technology without additional wiring Up to...

Page 6: ...nds If the battery is disconnected if its capacity is too low or if the battery voltage drops to 10 5 volts or less when there is no AC the Battery Trouble message will appear in the Trouble Display A...

Page 7: ...To metallic enclosure To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals COMBUS AUX POWER Refer to transformer req...

Page 8: ...ontact Modules DGP2 ZC1 _______ X 30mA __________ mA 1 Zone Expansion Modules DGP2 ZX1 _______ X 30mA __________ mA 4 Zone Expansion Modules APR3 ZX4 _______ X 30mA __________ mA 8 Zone Expansion Modu...

Page 9: ...0ft Magellan Module MG RCV3 A 35mA LCD Keypad DGP2 641BL D 110mA 15m 50ft 7 5m 25ft 7 5m 25ft 15m 50ft Motion Detector Module DGP2 70 E 30mA LED Keypad DGP2 648 F 110 mA LED Keypad DGP2 648 G 110 mA A...

Page 10: ...would exceed the system s capacity For information on how to assign a detection device to a zone in the control panel please refer to Zone Programming on page 11 Before connecting a module to the cont...

Page 11: ...shown in Figure 3 on page 3 2 14 Keyswitch Connections Connect the keyswitches to the keypad control panel or Zone Expansion Module s hardwired input terminals as shown in Figure 9 Once a keyswitch i...

Page 12: ...elay will cause the control panel to transmit the Fire Loop Trouble report if programmed in section 707 To reset unlatch the smoke detector after an alarm verify that the negative of the smoke detecto...

Page 13: ...the right action key Exit on Grafica keypads as many times as needed to return to the desired screen Please note that a module s serial number can be located on the module s PC board or it may already...

Page 14: ...that the write protect jumper is on 3 Enter section 965 to copy the contents of the panel except sections 001 to 048 device serial numbers and 049 to 056 keyswitch serial numbers to the key 966 to co...

Page 15: ...esent zones 1 to 48 respectively Zone Parameters Sections 101 to 148 represent zones 1 to 48 respectively Enter the 8 digit SERIAL NUMBER of the addressable detection device or module that has a hardw...

Page 16: ...ry Delay 1 Timer 230 Entry Delay 2 Timer 231 Entry Delay 3 Timer 232 Entry Delay 4 Timer 233 Please note these are the same timers used for Stay Delay zones see section 4 2 9 on page 13 Entry Delay zo...

Page 17: ...lay 4 Timer in section 233 Please note that the Entry Delay Timers are the same timers used for Entry Delay zones 4 3 Zone Partition Assignment SECTIONS 101 TO 148 SECOND DIGIT 1 TO 4 The control pane...

Page 18: ...digit delay value 010 to 255 seconds into section 200 Fire Zones cannot be set as Intellizones 4 4 7 Delay Alarm Transmission SECTIONS 101 TO 148 OPTION 8 When an alarm condition occurs on a zone wit...

Page 19: ...Panel 15 Table 5 Hebrew Keypad Letter Assignment Table 6 Russian Keypad Letter Assignment Table 7 Special Characters Catalogue Table 8 Hebrew Special Characters Catalogue Table 9 Russian Special Chara...

Page 20: ...t 004 speed 205 Panel Terminal 5 Input 005 speed 206 Panel Terminal 6 Input 006 speed 207 Panel Terminal 7 Input 007 speed 208 Panel Terminal 8 Input 008 speed 209 Panel Doubler 1 Input 009 speed 210...

Reviews: