30 Installer’s Guide
open for 45 seconds. Enter any value between 001 and 255 to
determine the seconds before the expiry of the Door Left Open
Interval that the reader will beep. (default = 15 seconds)
Figure 9: Pre-Alarm example
6.5.5 Door Left Open Alarm Feedback
Section [003]: Options [5] and [6]
An Access Control door is programmed with a Door Left Open
Interval (see section 6.5.2 on page 29). Once this interval has
expired, the Door Left Open Alarm can be either audible or silent
and will either beep as long as the Access Alarm is occurring or
follow the Beep Timer in section
[010]
. The sound of the Door
Left Open Alarm resembles the rapid beep generated during the
last ten seconds of the Exit Delay. When the door is closed
during an Access Alarm, the Door Left Open Restore event can
be logged in the Event Buffer.
Option
[5]
ON = The Door Left Open Alarm is audible. (default)
Option
[5]
OFF= The Door Left Open Alarm is silent.
If option
[5]
is enabled:
Option
[6]
ON = Door Left Open Alarm follows Beep Timer (section
[010]
)