28 Installer’s Guide
presented to the reader at 8AM on Monday. Although the
schedule started at 7AM, the door remained locked from 7AM to
8AM. Once access was granted at 8AM, the door remained
unlocked until 5PM.
Option
[1]
ON = Card activates Door Unlocked Schedule
Option
[1]
OFF= The Schedule activates without Card (default)
6.5 D
OOR
L
EFT
O
PEN
O
PTIONS
6.5.1 Door Left Open Access Alarm
Section [005]: Option [2]
When an Access Control door is opened after an Access Granted
or a Request for Exit, an Access Alarm can be generated if it not
closed within a certain period of time (see section 6.5.2 on
page 29).
Option
[2]
ON = Door Left Open Alarm is enabled. (default)
Option
[2]
OFF= Door Left Open Alarm will not be generated.
When the Door Left Open Alarm is disabled, the following
sections are also disabled:
Section
[003]
Option
[3]
Door Left Open Pre-alarm
Option
[5]
Door Left Open Alarm (audible/silent)
Option
[6]
Door Left Open Alarm follows (restore/timer)
[008]
Door Left Open Interval
[009]
Door Left Open Pre-alarm Timer
[010]
Beep Timer for Door Left Open Alarm
Summary of Contents for Digiplex DGP-641