USER MANUAL
UPS00100DC
©
Panduit Corp. 2018
IA-CD-0009 Rev. 07
Page
23
of
46
WARNING:
Over
Temperature
(Device
Operational)
If the device is in an environment that is above the operating
temperature, the Module Status in the WBI will be set to this status. The
corresponding MOD LED indicator shall be flashing red.
This warning is a notification to take the action by cooling down
the environment that the UPS is in or else the UPS will
permanently shut down.
WARNING:
End of
Service Life
(Device
Operational)
If the device is nearing its End of Life, the Module Status in the WBI
will be set to this status. The corresponding MOD LED indicator shall
be flashing red.
This warning is a notification to take the action to order a new
replacement UPS and install before the UPS transitions to End of
Life.
End of Life
If the device is at End of Life, the Module Status in the WBI will be set
to this status. The corresponding MOD LED indicator shall be
steady red.
The UPS will continue to allow pass-through power but will no
longer provide backup power.
5.4.2.
Input, Volts and Input, Amps
“Input, Volts” displays the DC Voltage present on the Input (INP 1+, INP 2-) terminals.
“Input, Amps” displays the total DC Current being used by the UPS and Output Load.
5.4.3.
Output, Volts and Output, Amps
“Output, Volts” displays the DC Voltage present on the Output (OUT 5+, OUT 6–) terminals. When Input
Power is present, this may be a slightly lower value than Input Volts due to small losses within the UPS
circuitry. When Input Power is not present, this value will be the nominal Output Voltage supplied by
the UPS from its internal stored energy.
5.4.4.
Load Sense, Amps
“Load Sense, Amps” displays the approximate current draw through the optional accessory Load Sense
Module (LSM) when connected in series with the power supply and the load. If the LSM is not being
used, this value will typically be near zero.
5.4.5.
Uptime, HHHHHH:MM:SS
“Uptime” displays elapsed time since the UPS has started operating with “H”, “M”, and “S” denoting
hours, minutes, and seconds. Up to a maximum of 999999 hours will be shown.
5.4.6.
Temperature, deg C.
“Temperature” displays the temperature inside the UPS enclosure. For normal operating conditions, the
Temperature displayed will be about 10 degrees higher than the UPS ambient temperature (outside its
enclosure).
5.4.7.
State of Health
“State of Health” (SOH) is based on the capacitance of the ELDC cells. A capacitance measurement will
automatically run once a week. The value displayed in the SOH field is the percentage of life left on the
UPS. A warning will be set in the Module Status field on this page when the UPS is
approaching
end of
life. It is recommended to purchase a replacement UPS when the “WARNING: End of Service Life” alert