4.4.
HARDWARE INSTALL
Figure 6: DIN Rail Installation
No minimum side-to-side spacing to other devices is required for proper operation of the UPS. However,
ensure there is ample space to cable components to protect the cabling integrity. Also ensure there is access
to the power switch, the LEDs, the reset button, and the Ethernet port on the underside of the device.
To install the UPS, place the module with the DIN rail guide on the top edge of the DIN rail and then snap it
downwards as shown in Figure 6: DIN Rail Installation. To remove the UPS, release the snap-on catch using a
standard screwdriver, tilt the unit up to detach the module from the bottom edge of the DIN rail as shown in
Figure 6: DIN Rail Installation then lift the unit off the top edge of the DIN rail.
4.5.
WIRING
This product is intended to be hardwired at the customer site/location. It must be installed by a qualified
electrician in compliance with all local and national regulations.
NOTE
:
The UPS should be shipped with the power switch in the ON position. Ensure that
the power switch is
in the OFF position
before installation
.
A typical configuration is where the UPS provides backup power to a load with redundant power source as
shown in Figure 7: System Wiring Diagram. The Primary Power Supply provides power to the load through the
optional load sense module (LSM). UPS SEN 3+ pin is connected to pin 3 of the LSM and UPS SEN 4- pin is
connected to pin 4 of the LSM.
Another configuration may be where the UPS provides backup power to a load with a single power source.
Using Figure 7: System Wiring Diagram to visualize this configuration, remove the Primary Power Supply, the
LSM and the associated wiring. Then relabel the Secondary Power Supply and the Secondary connection to
load as Primary. In this configuration no LSM is required and there will be no connections to the SEN pins on
the UPS.