18 Technical Data
18.1. Operation Characteristics
18.1.1.
WH-SD24BE5-1 WH-UD24BE5-1
Heating Characteristics at Different Outdoor Air Temperature and Piping Length
Condition:
Indoor water inlet temperature : 30
°
C
Indoor water outlet temperature : 35
°
C
Piping (m)
OD (
°
C)
Capacity (W)
Input Power (W)
Ampere (A)
HP (MPa)
Td (
°
C)
3
35
7000
1000
4.60
22.4
57.0
25
7000
1010
4.64
21.5
53.4
16
7000
1280
5.88
21.5
54.6
7
7000
1590
7.30
21.2
53.1
2
6450
2360
10.82
22.4
60.2
-7
6250
3200
14.67
23.7
75.1
-15
7200
3260
14.94
24.4
85.7
-20
4300
2440
11.19
23.0
81.9
7
35
7000
960
4.41
22.0
57.4
25
7000
980
4.51
21.8
54.0
16
7000
1250
5.74
21.5
53.3
7
7000
1590
7.30
21.5
52.9
2
6400
2320
10.64
22.3
60.6
-7
6200
3160
14.48
23.9
75.0
-15
7000
3180
14.57
24.0
81.5
-20
4200
2400
11.00
23.1
83.1
10
35
7000
960
4.41
21.7
59.4
25
7000
950
4.37
21.5
56.4
16
7000
1210
5.56
21.2
54.9
7
7000
1510
6.93
20.9
53.7
2
6250
2270
10.41
21.6
63.7
-7
6150
2970
13.61
23.1
75.8
-15
6750
3090
14.16
22.6
86.1
-20
4050
2050
9.40
21.3
85.1
20
35
6680
960
4.41
21.7
57.4
25
6900
950
4.37
21.5
54.5
16
6750
1210
5.56
21.2
52.0
7
7000
1510
6.93
20.9
53.2
2
6100
2180
10.00
21.2
64.0
-7
6050
2690
12.33
22.0
76.3
-15
6650
3000
13.75
22.3
87.2
-20
4000
1950
8.94
21.0
85.8
30
35
6500
960
4.41
21.6
58.4
25
6800
950
4.37
21.5
56.4
16
6600
1210
5.56
21.3
56.0
7
7000
1510
6.93
21.1
58.2
2
5980
2180
10.00
21.2
65.3
-7
6000
2640
12.10
22.2
79.0
-15
6550
2950
13.52
22.1
86.4
-20
3950
1900
8.72
20.8
84.8
Summary of Contents for WHSD24BE51
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 4 1 2 Main Components 4 2 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 71: ...71 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 72: ...72 17 5 To Remove Electronic Controller Board and Transformer 17 6 To Remove RCCB ...
Page 74: ...74 When reinstall the water pipe use grease or water at the joining ...
Page 79: ...79 18 3 Hydraulic Pump Performance ...
Page 82: ...82 19 2 WH UD24BE5 1 WH UD30BE5 1 ...
Page 83: ...83 ...