15 Maintenance Guide
In order to ensure optimal performance of the unit, checks and inspections on the unit and the field wiring must be carried out
regularly. Please request a licensed technician for carry out maintenance job.
Before carried out any maintenance or repair work, and removing the front plate of heat exchanger unit, always switch off all power
supply (i.e. indoor unit power supply, heater power supply and sanitary tank power supply).
Below checks must be carried out at least once a year.
1. Water pressure
Water pressure should not lower than 0.05 MPa (with inspects the pressure gauge). If necessary add tap water into boiler
tank. Refer to boiler tank installation instruction for details on how to add water.
2. Water filter
Clean the water filter in regularly basic.
• Water filter is located inside the tube connector which is below water pump. (Refer to figure below)
• Use spanner to detach the water pump’s bottom nut.
• Take out the filter carefully so that not deforms it shape.
• Use tap water only to wash the residue on the filter. If necessary, gently use soft brush only to clean the hard dirt.
• After clean, put it back to the original location and tighten the nut connection with torque wrench.
3. Pressure relief valve
• Check for correction operation of pressure relief valve by turn up the lever to become horizontal. (Refer to figure below)
• If you do not hear a clacking sound (due to water drainage), contact your local authorized dealer.
• Turn down the lever after checking finish.
• In case the water keeps drained out from the unit, switch off the system, and then contact your local authorized dealer.
4. Indoor unit control board area
Thorough visual inspection of the control board and look for defects, i.e. loose connection, melting of wire insulator and etc.
5. RCCB
Ensure the RCCB set to “ON” condition before check RCCB.
Turn on the power supply to the indoor unit.
This testing could only be done when power is supplied to the indoor unit.
• Push the “TEST” button on the RCCB. The lever would turn down and indicate “0” and indicate green colour if it functions
normal.
• Contact authorized dealer if the RCCB malfunction.
• Turn off the power supply to the indoor unit.
• If RCCB functions normal, set the lever to “ON” again after testing finish.
Becareful not to touch parts other than RCCB test button when the power is supplied to Indoor Unit. Else, electrical shock may
happen.
Summary of Contents for WHSD24BE51
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 4 1 2 Main Components 4 2 Outdoor Unit ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 23: ...23 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 71: ...71 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 72: ...72 17 5 To Remove Electronic Controller Board and Transformer 17 6 To Remove RCCB ...
Page 74: ...74 When reinstall the water pipe use grease or water at the joining ...
Page 79: ...79 18 3 Hydraulic Pump Performance ...
Page 82: ...82 19 2 WH UD24BE5 1 WH UD30BE5 1 ...
Page 83: ...83 ...