56
13.1.6 Low Pressure Protection Control
Purpose:
o
To protect the system operation.
o
Detection
period:
After compressor on for 5 minutes.
o
Detection
conditions:
When detection of Tem above 30°C.
Calculation of average evaporation temperature (Tem).
Use outdoor low pressure sensor.
Tem use the value calculated for discharge temperature setting value
o
After
detection:
Compressor stops restart again after 3 mins.
When abnormalities continuously generated 60 times within 480 minutes
Protection
is
prohibited.
Error H42 will be displayed.
13.1.7 High Pressure Sensor Control / Low Pressure Sensor
Purpose:
- To protect the system operation.
Detection
period:
- After compressor on for 1 minute.
Detection
conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
13.1.8 Outside Temperature Current Control
13.1.9 Extreme Low Temperature Control
Purpose:
- To improve the compressor reliability during cold start and after deice when running in extreme low outdoor
temperature -20°C.
Starting condition:
1 Heating
operation
2 Outdoor air temperature < -10°C
3 Actual
frequency
≥
50Hz
4 Compressor discharge temperature < 20°C
When the above condition is fulfilled, this control is activated.
5Hz up every 30 sec. until it reaches the target frequency.
Cancellation condition:
- starting condition not fulfill.
- Cancel the extreme low temperature control when compressor discharge sensor
≥
60°C
Summary of Contents for WH-SHF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up the Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SHF09D3E5 ...
Page 22: ...22 8 1 2 WH SHF12D6E5 ...
Page 23: ...23 8 2 Outdoor Unit ...
Page 24: ...24 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SHF09D3E5 ...
Page 25: ...25 9 1 2 WH SHF12D6E5 ...
Page 26: ...26 9 2 Outdoor Unit ...
Page 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 53: ...53 ...
Page 102: ...102 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 103: ...103 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 110: ...110 19 2 WH UH09DE5 WH UH12DE5 ...
Page 111: ...111 ...