49
12.9 Indoor Back-Up Heater Control
12.9.1 Indoor Electric Heater Control
1 Normal Heating Mode
o
Heater
On
condition:
a. Heater switch is ON
b. After Heatpump thermo ON for
[30]
mins
c. After water pump operate
[9]
mins
d. Outdoor air temperature < Outdoor set temperature for heater
e.
[20]
minutes since previous Backup heater Off
* When heatpump cannot operate due to error happens during normal operation, heater will go into
force mode automatic
* Heater need to operate during deice operation
f. When water outlet temperature < Water set tempe
[-8
°
C]
(check water out temperature
before ON heater 3 and check also water out temperature after heater delay timer before ON heater
2 and 1)
o
Heater Stop Condition:
a. When outdoor set temperature > outdoor set tempe
[+2
°
C]
for continuous 15 secs OR
b. When water out temp> water set tempe
[-2
°
C]
for continuous 15 secs OR
c. Heater switch is Off OR
d. Heat pump thermo-off or OFF condition
2 Force
Heater
Mode
o
Heater On Condition:
a. After water pump operate
[9]
mins
b. When water outlet temperature < water set tempe
[-8
°
C]
c.
[20]
minutes since previous Backup heater Off
o
Heater Stop condition
a. Force mode off
OR
b. When water outlet temperature > water set tempe
[-2
°
C]
for continuous 15 secs
* Do not operate heater at the following situation
1 Water outlet temperature sensor, and water inlet sensor abnormal
2 Flow switch abnormal
3 Circulation pump stop condition
4 During Heatpump switch to tank side
Summary of Contents for WH-SHF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up the Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SHF09D3E5 ...
Page 22: ...22 8 1 2 WH SHF12D6E5 ...
Page 23: ...23 8 2 Outdoor Unit ...
Page 24: ...24 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SHF09D3E5 ...
Page 25: ...25 9 1 2 WH SHF12D6E5 ...
Page 26: ...26 9 2 Outdoor Unit ...
Page 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 53: ...53 ...
Page 102: ...102 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 103: ...103 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 110: ...110 19 2 WH UH09DE5 WH UH12DE5 ...
Page 111: ...111 ...