41
Booster heater control
- Booster heater turn On and Off follow normal operation.
- Booster heater turn ON condition:
1 During startup time (initialization), Booster heater turn ON after DELAY TIMER.
2 When tank temperature lower than HEATER ON TEMP
3 20 minutes from previous heater off.
- Booster heater turn OFF condition:
1 When tank temperature higher than tank set temperature for continuous 15 secs.
Solar 3 way valve
- Solar pump operates follow solar operation specification.
2 way valve closes
Others
- Indoor backup heater cannot be ON during tank mode only.
12.1.4 Heat + Tank Mode Operation
Setting 1: When Heating priority is set by control panel:
1 3 ways valve control:
o
3 ways valve switch to room side during External Room Thermo ON
OR
Solar 3ways valve ON
OR
Tank
Thermo OFF time, and switch to tank side at External Room Thermo OFF
AND
Solar 3 ways valve OFF
2 Heat pump operation control:-
o
During External Room Thermo ON time:
(When room thermo ON, heat pump must operate to room
side)
Heat pump operate follow normal operation at room side
o
During External Room Thermo OFF time:
Switch 3 ways valve to tank side, IF
Under Solar Priority Set condition:
o
Tank temperature < Tank THERMO ON TEMP
AND
Solar Valve OFF
Under Solar Priority Not Set condition:
o
Tank temperature < Tank THERMO ON TEMP
Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF
o
External Room Thermo ON back
OR
Under Solar Priority Set condition:
Tank temperature > Tank THERMO OFF TEMP. for continuous 3 minutes
OR
Solar Valve
ON
Under Solar Priority Not Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 3 minutes
* THERMO ON and THERMO OFF point refer to case below.
Operation condition when 3 ways valve switch to tank side:
Tank water set temperature = tank set temperature or [60
°
C] whichever lower
Heat Pump Water Outlet set temperature is set to [63
°
C] during tank interval
Initial Tank THERMO ON TEMP = heat pump tank target tempe
[-2°C]
Case 1:
o
THERMO OFF TEMP:
1.
THERMO OFF TEMP = Heat pump tank target tempe
[0
°
C]
.
2.
Tank temperature > THERMO OFF TEMP for continuous 10 minutes after compressor off, switch 3
ways valve to room side.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-2
°
C]
or
2.
If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF, switch to tank side.
Summary of Contents for WH-SHF09D3E5
Page 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 11: ...11 ...
Page 12: ...12 ...
Page 13: ...13 4 1 2 Weekly Timer Setting ...
Page 14: ...14 4 1 3 Setting Up the Special Functions ...
Page 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Page 17: ...17 5 2 Outdoor Unit ...
Page 19: ...19 ...
Page 20: ...20 7 Block Diagram ...
Page 21: ...21 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SHF09D3E5 ...
Page 22: ...22 8 1 2 WH SHF12D6E5 ...
Page 23: ...23 8 2 Outdoor Unit ...
Page 24: ...24 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SHF09D3E5 ...
Page 25: ...25 9 1 2 WH SHF12D6E5 ...
Page 26: ...26 9 2 Outdoor Unit ...
Page 27: ...27 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 53: ...53 ...
Page 102: ...102 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 103: ...103 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 110: ...110 19 2 WH UH09DE5 WH UH12DE5 ...
Page 111: ...111 ...