68
13. Protection Control
13.1 Protection Control for All Operations
13.1.1 Time Delay Safety Control
1 The compressor will not start for three minutes after stop of operation.
13.1.2 30 Seconds Forced Operation
1 Once the compressor starts operation, it will not stop its operation for 30 seconds.
2 However, it can be stopped using control panel at indoor unit.
13.1.3 Total Running Current Control
1 When the outdoor running current exceeds X value, the compressor frequency will decrease.
2 If the outdoor running current does not exceed X value, the compressor frequency will return to normal
operating frequency.
3 If the outdoor running current continue to increase till exceed Y value, compressor will stop, and if this occurs
3 times within 20 minutes, system will stop operation and OFF/ON control panel LED will blink (F16 error
occurs).
09C
12C
14C
16C
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Heating
6.2 10.6 7.4 10.6 8.0 10.6 8.5 10.6
Cooling
6.3 10.6 6.6 10.6 7.9 10.6 8.5 10.6
13.1.4 IPM (Power Transistor) Prevention Control
A. Overheating Prevention Control
1 When the IPM temperature rises to 95°C, compressor will stop immediately.
2 Compressor will restart delay 3 minutes when the IPM temperature decreases to 90°C.
If this condition repeats continuously 3 times within 30 minutes, system will stop operation and OFF/ON
control panel LED will blink (F22 error occurs).
B. DC Peak Current Control
1 When the current to IPM exceeds set value of 40.1 ± 5.0 A (UD09CE), 44.7 ± 5.0 A (UD12CE, UD14CE and
UD16CE), compressor will stop. Compressor will restart after three minutes.
2 If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart
after two minutes.
3 If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after
one minute. If this condition repeats continuously for seven times, system will stop operation and OFF/ON
control panel LED will blink (F23 error occurs).
13.1.5 Compressor
Overheating Prevention Control
The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in
below figures. When the compressor tank temperature exceeds 112°C, compressor will stop, and if this occurs 4
times within 30 minutes, system will stop operation and OFF/ON control panel LED will blink (F20 error occurs).
Summary of Contents for WH-SDC09C3E8
Page 14: ...14 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 4 1 2 Weekly Timer Setting ...
Page 18: ...18 4 1 3 Setting Up the Special Functions ...
Page 19: ...19 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 20: ...20 5 Dimensions 5 1 Indoor Unit ...
Page 21: ...21 5 2 Outdoor Unit ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH UD09CE8 ...
Page 25: ...25 7 2 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC09C3E8 ...
Page 27: ...27 8 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Page 28: ...28 8 2 Outdoor Unit ...
Page 29: ...29 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC09C3E8 ...
Page 30: ...30 9 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Page 31: ...31 9 2 Outdoor Unit ...
Page 32: ...32 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 33: ...33 10 1 2 Solar Printed Circuit Board Optional ...
Page 34: ...34 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 35: ...35 10 2 2 Noise Filter Printed Circuit Board ...
Page 50: ...50 Solar Priority is Set Solar Priority is Not Set ...
Page 53: ...53 Heat Tank Heating No Priority Solar Priority Set ...
Page 54: ...54 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 64: ...64 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 65: ...65 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 113: ...113 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 114: ...114 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 137: ...137 19 2 WH UD09CE8 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Page 138: ...138 ...