49
ii. Case 2
- Heatpump THERMO OFF TEMP:
1 Heatpump THERMO OFF TEMP = 55°C +
[+2°C]
.
2 Water outlet temperature > Heatpump THERMO OFF TEMP for continuous 3 minutes, heatpump OFF but
water pump ON.
- Heatpump THERMO ON TEMP:
1 Heatpump THERMO ON TEMP = Water inlet during thermo off time +
[-3°C]
.
2 Heatpump ON back when water outlet temperature < Heatpump THERMO ON TEMP
iii. Case 3
- Heatpump THERMO OFF TEMP:
1 Water inlet temperature > 52°C for continuous 60 sec, heatpump OFF and water pump OFF
- Heatpump THERMO ON TEMP:
1 Heatpump THERMO ON TEMP = Water inlet during thermo off time +
[-3°C]
.
2 Heatpump ON back when water outlet temperature < Tank temp. when heatpump thermo off +
[-3°C]
3 Heatpump only ON back after water outlet temperature < Heatpump THERMO ON TEMP & water pump ON
for 3 minutes.
Booster heater control
1 Booster heater turn On and OFF follow normal operation.
2 Booster heater turn ON condition:
o
During startup time (initialization), Booster heater turn ON after DELAY TIMER.
o
When tank temperature lower than HEATER ON TEMP
o
20 minutes from previous heater off.
3 Booster heater turn OFF condition:
o
When tank temperature higher than tank set temperature for continous 15 sec.
Solar 3 way valve
- Solar pump operates follow solar operation specification.
2 ways valve control:
- 2 ways valve close
Others
- Indoor backup heater cannot be On during tank mode only.
Summary of Contents for WH-SDC09C3E8
Page 14: ...14 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 4 1 2 Weekly Timer Setting ...
Page 18: ...18 4 1 3 Setting Up the Special Functions ...
Page 19: ...19 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 20: ...20 5 Dimensions 5 1 Indoor Unit ...
Page 21: ...21 5 2 Outdoor Unit ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH UD09CE8 ...
Page 25: ...25 7 2 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC09C3E8 ...
Page 27: ...27 8 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Page 28: ...28 8 2 Outdoor Unit ...
Page 29: ...29 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC09C3E8 ...
Page 30: ...30 9 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Page 31: ...31 9 2 Outdoor Unit ...
Page 32: ...32 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 33: ...33 10 1 2 Solar Printed Circuit Board Optional ...
Page 34: ...34 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 35: ...35 10 2 2 Noise Filter Printed Circuit Board ...
Page 50: ...50 Solar Priority is Set Solar Priority is Not Set ...
Page 53: ...53 Heat Tank Heating No Priority Solar Priority Set ...
Page 54: ...54 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 64: ...64 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 65: ...65 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 113: ...113 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 114: ...114 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 137: ...137 19 2 WH UD09CE8 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Page 138: ...138 ...