13.2 Protection Control for Heating Operation
13.2.1 Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid
compressor overloading.
13.2.2 Deice
Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor
stop.
13.3 Protection Control for Cooling Operation
13.3.1 Outdoor Air Temperature Control
The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor
frequency will adjust base on outdoor air temperature.
13.3.2 Freeze Prevention Control 1
1 When indoor heat exchanger temperature is lower than 0°C continuously for 10 seconds, compressor will
stop operating.
2 Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 1°C.
3 Indoor heat exchanger freeze prevention (H99) will memory in error history.
Summary of Contents for WH-SDC09C3E8
Page 14: ...14 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 4 1 2 Weekly Timer Setting ...
Page 18: ...18 4 1 3 Setting Up the Special Functions ...
Page 19: ...19 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 20: ...20 5 Dimensions 5 1 Indoor Unit ...
Page 21: ...21 5 2 Outdoor Unit ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH UD09CE8 ...
Page 25: ...25 7 2 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC09C3E8 ...
Page 27: ...27 8 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Page 28: ...28 8 2 Outdoor Unit ...
Page 29: ...29 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC09C3E8 ...
Page 30: ...30 9 1 2 WH SDC12C9E8 WH SDC14C9E8 WH SDC16C9E8 ...
Page 31: ...31 9 2 Outdoor Unit ...
Page 32: ...32 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 33: ...33 10 1 2 Solar Printed Circuit Board Optional ...
Page 34: ...34 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Page 35: ...35 10 2 2 Noise Filter Printed Circuit Board ...
Page 50: ...50 Solar Priority is Set Solar Priority is Not Set ...
Page 53: ...53 Heat Tank Heating No Priority Solar Priority Set ...
Page 54: ...54 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 64: ...64 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 65: ...65 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 113: ...113 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Page 114: ...114 17 5 To Remove RCCB 17 6 To Remove Transformer and Electronic Controller Board ...
Page 137: ...137 19 2 WH UD09CE8 WH UD12CE8 WH UD14CE8 WH UD16CE8 ...
Page 138: ...138 ...