48
Switch back 3 ways valve to room side, Heat pump and water pump turn OFF, IF
o
External Room Thermo ON back
OR
Under Solar Priority Set condition:
Tank temperature > Tank THERMO OFF TEMP. for continuous 3 minutes
OR
Solar Valve
ON
Under Solar Priority Not Set condition:
Tank temperature > Tank THERMO OFF TEMP for continuous 3 minutes
* THERMO ON and THERMO OFF point refer to case below.
Operation condition when 3 ways valve switch to tank side:
Tank water set temperature = tank set temperature or [50
°
C] whichever lower
Heat Pump Water Outlet set temperature is set to [53
°
C] during tank interval
Initial Tank THERMO ON TEMP = heat pump tank target tempe
[-1°C]
Case 1:
o
THERMO OFF TEMP:
1.
THERMO OFF TEMP = Tank water set tempe
[1
°
C]
.
2.
Tank temperature > THERMO OFF TEMP for continuous 10 seconds after compressor off, switch 3
ways valve to room side.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-1
°
C]
or
2.
If tank temperature < THERMO ON TEMP
AND
External Room Thermo OFF, switch to tank side.
Case 2:
o
Heat pump THERMO OFF TEMP:
1.
Heat pump THERMO OFF TEMP = 53°C +
[+4
°
C]
.
2.
Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 3 minutes, heat pump
OFF.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet when heat pump THERMO OFF +
[-3
°
C]
.
2.
If water outlet temperature < THERMO ON TEMP
AND
External Room Thermo OFF, heat pump ON.
Case 3:
o
Heat pump THERMO OFF TEMP:
1.
Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
o
Next THERMO ON TEMP:
1.
THERMO ON TEMP = Water inlet temperature < 55°C.
2.
If water inlet temperature < THERMO ON TEMP AND External Room Thermo OFF, heat pump ON.
Case 4: (Only during solar priority is set condition)
o
When solar request ON, solar valve will ON and switch 3 ways valve to room side
o
THERMO ON TEMP:
1.
THERMO ON TEMP = Heat pump tank target tempe
[-1
°
C]
.
2.
If tank temperature < THERMO ON TEMP AND External Room Thermo OFF
AND
Solar 3WV OFF,
switch to tank side.
3 Backup Heater control:-
o
During External Room Thermo ON time, follow normal backup heater control operation
o
During External Room Thermo OFF time, Backup heater OFF
4 Booster heater control:
o
Booster heater On/Off follow normal operation.
* Under solar priority is set condition, when solar 3 way valve is ON, booster heater turn OFF.
Summary of Contents for WH-MXF09D3E8
Page 10: ...10 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Mono bloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 24: ...24 8 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 28: ...28 9 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 33: ...33 10 2 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Mono bloc Unit Dimension Diagram ...
Page 35: ...35 Main Components ...
Page 46: ...46 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 63: ...63 ...
Page 111: ...111 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 118: ...118 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 119: ...119 ...
Page 123: ...123 19 2 Water System ...