16.5.34 Cooling High Pressure Overload Protection (F95)
Malfunction Decision Conditions:
During operation of cooling, when pressure 4.0MPa and above is detected by outdoor high pressure sensor.
Malfunction Caused:
1 Dust accumulation in the outdoor unit heat exchanger.
2 Air short circuit at outdoor unit.
3 2 way valve closed.
4 Faulty outdoor unit fan motor.
5 Clogged expansion valve or strainer.
6 Excessive
refrigerant.
7 Faulty outdoor high pressure sensor.
8 Faulty outdoor unit PCB (main).
Summary of Contents for WH-MXF09D3E8
Page 10: ...10 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Mono bloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 24: ...24 8 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 28: ...28 9 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 33: ...33 10 2 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Mono bloc Unit Dimension Diagram ...
Page 35: ...35 Main Components ...
Page 46: ...46 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 63: ...63 ...
Page 111: ...111 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 118: ...118 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 119: ...119 ...
Page 123: ...123 19 2 Water System ...