39
Connecting with external device (optional)
1. All connections shall follow to the local national wiring standard.
2. It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
3. Maximum output power of booster heater shall be
≤
3 kW. Booster Heater cord must be (3 x min 1.5 mm
2
), of
type designation 60245 IEC 57 or heavier.
4. Two-way Valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details. Valve
cable shall be (3 x min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation
sheathed cable.
* note: - Shall be CE marking compliance component.
- Maximum load for the valve is 9.8VA.
* Cooling model only
5. Three-way Valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details. Valve
cable shall be (3 x min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation
sheathed cable.
* note: - Shall be CE marking compliance component.
- It shall be directed to heating mode when it is OFF.
- Maximum load for the valve is 9.8VA.
6. Room Thermostat cable must be (4 or 3 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or
polychloroprene sheathed cable.
7. Tank OLP cable must be (2 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene
sheathed cable.
* note: - if such connection deemed NO necessary for tank OLP, please connect jumper between terminal
no. 13 and 14.
8. Tank Sensor shall be resistance type, please refer to Graph 4.1 for the characteristic and details of sensor. Its
cable shall be (2 x min 0.3 mm
2
), double insulation layer (with insulation strength of min 30V) of PVC-sheathed or
polychloroprene sheathed cable.
9. External Controller shall be connected to 1-pole switch with min 3.0mm contact gap. (connection refer to Diagram
4.2). Its cable must be (2 x min 0.5 mm
2
), double insulation layer of PVC-sheathed or polychloroprene sheathed
cable.
* note: - When making such connection, kindly remove the jumper between terminal no. 17 and 18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
rms
.
10. Must install Solar Connection PCB (optional) to Mono bloc unit when Solar Pump Station is utilized. Refer Solar
Connection PCB’s installation instruction for detail of installation.
11. Solar Three-way Valve cable shall be (3 x min 0.5 mm
2
), double insulation layer PVC-sheathed or
polychloroprene sheathed cable.
12. Solar Pump Station cable shall be (2 x min 0.5 mm
2
), of double insulation PVC-sheathed or polychloroprene
sheathed cable. Strongly recommended install with maximum length of 10 meter only.
Terminal screw
Tightening torque
N•cm { kgf•cm}
M4
157 ~ 196 {16 ~ 20}
M5
196 ~ 245 {20 ~ 25}
Summary of Contents for WH-MXF09D3E8
Page 10: ...10 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Mono bloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 24: ...24 8 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 28: ...28 9 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 33: ...33 10 2 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Mono bloc Unit Dimension Diagram ...
Page 35: ...35 Main Components ...
Page 46: ...46 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 63: ...63 ...
Page 111: ...111 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 118: ...118 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 119: ...119 ...
Page 123: ...123 19 2 Water System ...