66
13.1.6 Low Pressure Protection Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 5 minutes.
Detection
conditions:
o
When detection of Tem above 30°C.
o
Calculation of average evaporation temperature (Tem).
o
Use outdoor low pressure sensor.
o
Tem use the value calculated for discharge temperature setting value
After
detection:
o
Compressor stops restart again after 3 mins.
o
When abnormalities continuously generated 60 times within 480 minutes
o
Protection
is
prohibited.
o
Error H42 will be displayed.
13.1.7 High Pressure Sensor Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 1 minute.
Detection
conditions:
o
When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
o
When abnormality is detected continue 5 seconds, unit stop operation.
o
OFF/ON remote control LED will blink (H64 error occurs).
13.1.8 Outside Temperature Current Control
13.1.9 Extreme Low Temperature Control
Purpose:
- To improve the compressor reliability during cold start and after deice when running in extreme low outdoor
temperature -20°C.
Starting
condition:
o
Heating
operation
o
Outdoor air temperature < -10°C
o
Actual
frequency
≥
50Hz
o
Compressor discharge temperature < 20°C
When the above condition is fulfilled, this control is activated.
5Hz up every 30 sec. until it reaches the target frequency.
Cancellation
condition:
o
starting condition not fulfill.
o
Cancel the extreme low temperature control when compressor discharge sensor
≥
60°C
Summary of Contents for WH-MXF09D3E8
Page 10: ...10 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 ...
Page 15: ...15 4 1 4 Basic Operation 4 1 5 Advance Operation ...
Page 16: ...16 4 1 6 Weekly Timer Setting ...
Page 17: ...17 5 Dimensions 5 1 Mono bloc Unit ...
Page 18: ...18 6 Refrigeration And Water Cycle Diagram ...
Page 19: ...19 ...
Page 22: ...22 8 Wiring Connection Diagram 8 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 24: ...24 8 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 26: ...26 9 Electronic Circuit Diagram 9 1 WH MXF09D3E8 WH MXF09D3E8 1 ...
Page 28: ...28 9 2 WH MXF12D9E8 WH MXF12D9E8 1 ...
Page 30: ...30 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 31: ...31 10 1 2 Solar Printed Circuit Board Optional ...
Page 33: ...33 10 2 2 Noise Filter Printed Circuit Board ...
Page 34: ...34 11 Installation Instruction Mono bloc Unit Dimension Diagram ...
Page 35: ...35 Main Components ...
Page 46: ...46 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 63: ...63 ...
Page 111: ...111 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 118: ...118 19 Exploded View and Replacement Parts List 19 1 Refrigerant System ...
Page 119: ...119 ...
Page 123: ...123 19 2 Water System ...