283
25.2.36 Indoor Water Inlet Temperature Sensor Abnormality (- / - / F37)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet
temperature sensor are used to determine sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.
Troubleshooting:
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Indoor Refrigerant Liquid / Water Inlet / Water
Outlet Sensor Characteristic
-10
0
10
20
30
40
50
50
60
70
80
90
100
110
120
40
30
10
20
0
Temperature (°C)
Res
istan
ce (K
)
No
No
Yes
Yes
Check the CN-TH1 connector connnection:
- Turn OFF the power.
- Check the connector connection.
- Connector poor contact.
- Correct the connection.
- Defect in indoor water inlet
temperature sensor.
- Replace the indoor water inlet
temperature sensor.
- Defect in indoor unit PCB (main).
- Replace the indoor unit PCB (main).
Check the indoor water inlet temperature sensor:
- Plug out connector from the indoor unit PCB (main).
- Measure the resistance of the indoor water inlet
temperature sensor.
Is the CN-TH1 connector
connection normal?
Is the measured resistance of the
indoor water inlet temperature sensor
matches the value specified in its
characteristic chart?
Caution