93
27. Sterilization
Initial setting: 65°C 10min
②
① ③
Set timer to perform sterilization.
①
Set operating day & time. (Weekly timer format)
②
Sterilization temp (55~75°C
If use back-up heater, it is 65°C)
③
Operation time (Time to run sterilization when it reached setting temp
5min ~ 60min)
User shall set whether to use or not to use sterilization mode.
28. Force DHW Temp.
Initial setting: 35°C
Room H
Tank Heating
Tank Heating only
35°C
Set tank temperature to perform force DHW:
(When tank temperature drop below set point, will switch to tank only mode
and have higher priority for heat pump to heat up tank water by temporarily
stop room units operation.
Setting range is 25°C ~ 40°C
11.3.3.5 Service
Setup
29. Pump maximum speed
Initial setting: Depend on model
Service setup
12:00am,Mon
Flow rate Max. Duty Operation
88:8 L/min 0xCE
Air Purge
Select
Normally setting is not necessary.
Please adjust when need to reduce the pump sound etc.
Besides that, it has Air Purge function.
When *Pump flow setting is Max. Duty, this duty set is the fix pump duty run
during room side operation.
30. Dry concrete
30°C
1
2
3
4
5
6
35°C
35°C
40°C
40°C
45°C
Stage
Operate concrete curing operation.
Select Edit, set temp for every stage (1~99 1 is for 1 day).
Setting range is 25~55°C
When it is turned ON, dry concrete starts.
When it is 2 zone, it dries both zones.
31. Service contact
Contact-1: Bryan Adams
ABC/ abc
0-9/ Other
A B C D E F G H I J K L M N O P Q R
S T U V W X Y Z a b c d e f g h i
j k l m n o p q r s t u v w x y z
Select
Enter
Service setup
12:00am,Mon
Service contact:
Contact 1
Contact 2
Select
Confirm
Able to set name & tel no. of contact
person when there is breakdown
etc. or client has trouble. (2 items)