240
24.2.2 E01 & E02
E01 - Remote Controller Reception Error
E02 - Remote Controller Transmission Error
When remote controller is set to sub (Slave) remote controller:
If only one remote controller is connected to indoor unit, this remote controller
must set to main remote controller. (Wireless remote controller set the switch
at wireless receiver)
Group control:
Confirm the grouped indoor units no more than eight units.
Check all indoor unit power supply status.
Make sure group control setting is executed.
Group control wiring changed after setting is done.
Grouped control wire (Black & White) shorted, mis-wiring, wrong contact or
grounded.
Setting Related:
CHK and TEST pin shorted.
EEPROM no installed or defect when main power switched ON.
Remote controller on check mode.
Remote controller itself defect.
Indoor unit PCB malfunction.
EEPROM
TEST Pin
CHK Pin