3-5 Auxiliary Output Function (Non-safety Output)
This device is equipped with auxiliary output as non-safety application.
Terminal
No.
Names
Description
ERR
Lockout output
OFF for lockout
SUB
Auxiliary output
Negative logic output of control output 1 / 2 (OSSD 1 / 2)
AUX1
Sensor monitoring output 1 Monitor output corresponding to detection auxiliary output of sensor No. 1
AUX2
Sensor monitoring output 2 Monitor output corresponding to detection auxiliary output of sensor No. 2
AUX3
Sensor monitoring output 3 Monitor output corresponding to detection auxiliary output of sensor No. 3
AUX4
Sensor monitoring output 4 Monitor output corresponding to detection auxiliary output of sensor No. 4
<Time chart of lockout output>
<Time chart of auxiliary output>
<Time chart of senosr monitor outputs 1 to 4>
Do not use the auxiliary output for the purpose of stopping the machine in which
this device is mounted. Otherwise, death or injury may occur.
3-6
Lockout Cancel Function
After removing cause of the error, The lockout can be canceled by method listed below.
1) Tuns ON power supply again.
2) Reset operation from reset input terminal.
<
Manual reset
>
After short circuit between X1 and X2 30ms or more, open again.
<
Auto reset
>
After open between X1 and X3 30ms or more, short circuit again.
Functions
Normal
Error
Controller
operation
ON
OFF
Lockout output
(ERR)
ON
OFF
Sub detection of
sensors No.1 to 4
ON
OFF
Sensor monitor
output 1 to 4
(AUX1 to 4)
10ms or less
10ms or les
ON
OFF
Auxiliary output (SUB)
(Negative logic of OSSD)
Control output 1 / 2
(OSSD 1 / 2)
ON
OFF
100ms or less