22
© Panasonic Industriar Devices SUNX Co., Ltd. 2016
Functions
<Time chart>
3-2-2 Auto reset
When the detecting output of sensor is ON (without liquid leak), control outputs 1 / 2 (OSSD 1 / 2)
can be automatically ON.
To monitor an external device, a back check circuit (KA, KB) should be prepared between X1
and X3. If a back check circuit (KA, KB) is not required, the circuit between X1 and X3 should
be shorted.
<When back check circuit is required>
<When back check circuit is not required>
Note: The reset will be canceled in case cleaning of sub detection part is not enough or detecting auxiliary out
-
put (white) of safety leak sensor is broken.
When this device is operated in auto reset, auto recovery of the system after
control output shutoff should be prevented with a safety relay unit.
(From EN 60204-1)
<Time chart>
X1
X2
KA
KB
X1
X2
ON
OFF
Sensor detection
output
ON
OFF
Control output 1 / 2
(OSSD 1 / 2)
20ms or less
100ms or less
30ms or more
Open
Short-
circuit
Reset input
ON
OFF
Sensor detection
output
30ms or more
ON
OFF
Control output 1 / 2
(OSSD 1 / 2)
20ms or less
100ms or less