3) Transmission mode setting switch, I/O control number setting switch (SW2)

This switch sets each system setting. The transmission mode setting switch (SW2-1, SW2-2) per-

forms A mode, B mode and C mode setting. Furthermore, the I/O control number is set with the 

I/O control number setting switch.

Setting is read in only once when power is supplied to the computer. Changing the mode switch 

setting during operation is ineffective. (The setting cannot be changed with the reset command on 

the 

S-LINK V

 system side.)

Transmission mode setting switch

Transmission mode

SW2-1

SW2-2

A mode

OFF

OFF

B mode

OFF

ON

C mode

ON

OFF

(A mode)

ON

ON

I/O control number setting switch

I/O control

number

SW2-5

SW2-6

SW2-7

SW2-8

32 points

OFF

OFF

OFF

OFF

64 points

OFF

OFF

OFF

ON

96 points

OFF

OFF

ON

OFF

128 points

OFF

OFF

ON

ON

160 points

OFF

ON

OFF

OFF

192 points

OFF

ON

OFF

ON

224 points

OFF

ON

ON

OFF

256 points

OFF

ON

ON

ON

288 points

ON

OFF

OFF

OFF

320 points

ON

OFF

OFF

ON

352 points

ON

OFF

ON

OFF

384 points

ON

OFF

ON

ON

416 points

ON

ON

OFF

OFF

448 points

ON

ON

OFF

ON

480 points

ON

ON

ON

OFF

512 points

ON

ON

ON

ON

ON

1

7 8

5

SW2

6

4

2 3

Unused

Above diagram shows 

in case the transmission 

mode is set to B mode, 

and the I/O control points 

is set to 128 points.

4) I/O setting switch (SW3, SW4)

I/O setting is done for each 32 points with the I/O setting switch (SW3, SW4). Setting is read in 

only once when power is supplied to the computer or when the reset command is executed on 

the 

S-LINK V

 system side.

Changing the switch setting during operation is ineffective.

No.

Address

ON

OFF

SW3

1

0 to 31

Input

Output

2

32 to 63

3

64 to 95

4

96 to 127

5

128 to 159

6

160 to 191

7

192 to 223

8

224 to 255

SW4

1

256 to 287

2

288 to 319

3

320 to 351

4

352 to 383

5

384 to 415

6

416 to 447

7

448 to 479

8

480 to 511

Note: When setting I/O through a program, set all the 

switches to input (ON).

SW3

ON

1

7 8

5 6

4

2 3

SW4

ON

1

7 8

5 6

4

2 3

Above diagram shows in 

case input is set to 0 to 127 

and 256 to 383, while output 

is set to 128 to 255 and 384 

to 511.

Summary of Contents for S-LINK V

Page 1: ...2018 3 panasonic net id pidsx global Flexible Wire saving Link S LINK V PCI Bus S LINK V Control Board SL VPCI Instruction Manual CMJE SLVPCI No 0062 88V...

Page 2: ...e Take care that wrong wiring will damage the product Wiring This product has been developed produced for industrial use only In case noise generating equipment switching regulator inverter motor etc...

Page 3: ...Remarks 7 F G Frame ground 6 24V External power supply input 5 0V 4 24V Brown 3 0V Blue 2 D White 1 G Black Tightening torque of the terminal screws 0 5 to 0 6 N m Terminal block connector MSTB2 5 7 S...

Page 4: ...nts ON OFF OFF OFF 320 points ON OFF OFF ON 352 points ON OFF ON OFF 384 points ON OFF ON ON 416 points ON ON OFF OFF 448 points ON ON OFF ON 480 points ON ON ON OFF 512 points ON ON ON ON ON 1 7 8 5...

Page 5: ...during no transmission Blinking interval differs depending on the transmission speed A mode Fast C mode Slow 7 Busy indicator Orange It lights up during the system setting or transmission process con...

Page 6: ...6 S LINK V I O unit connected node number R HML0 47 Not usable 04 HML0 48 Error No Error state R HML0 49 Command execution request register Communication frame confirmation Error No clear Default Syst...

Page 7: ...2 HML0 19 207 206 205 204 203 202 201 200 HML0 1A 215 214 213 212 211 210 209 208 HML0 1B 223 222 221 220 219 218 217 216 HML0 1C 231 230 229 228 227 226 225 224 HML0 1D 239 238 237 236 235 234 233 23...

Page 8: ...s the first address of the affected S LINK V I O unit is indicated When each bit is 1 output of S LINK V output unit of the address short circuits or the I O driv ing power breaks down In case Bank ch...

Page 9: ...data area to the information corresponding to the bank number SL VPCI The internal circuit switches to the bank change over response register and then writes in the bank number User s computer It read...

Page 10: ...on When setting is done by a program I Os can be set in units of 16 In this case set all the I O set ting switches to input 0 ON If the change is done by program it is automatically changed within 1 t...

Page 11: ...rval shorter than the S LINK V system response delay time the data may not be transmitted After the output data is written if 1 is written into HML0 49 bit 0 and the next output data is written in aft...

Page 12: ...an interruption occurrence Only clearance of the interruption can be carried out 1 0 1 0 Command execution request register Command completion response register The order of priority for each command...

Page 13: ...In case bit 1 is 1 an interruption occurs and in case it is 0 an interruption does not occur If the input change interruption is effective an interruption occurs when the input signal of S LINK V inp...

Page 14: ...ntents of error check by 5 HML0 48 Error No Error state Occurrence Interruption Error In order to clear the interruption 6 Command execution request register 7 Command completion response register are...

Page 15: ...ency 0 75mm amplitude in X Y and Z directions for two hours each Shock resistance Note 5 98m s2 acceleration approx 10G in X Y and Z directions for three times each Grounding method Bracket Floating S...

Page 16: ...practice at the time of purchase or contract 4 Failure caused by use which deviates from the conditions environment given in the product catalogue or specifications 5 In case this product is used by...

Reviews: