1
1-11-2-1-13
(B) When an obstruction is present on the air outlet side
When the upward area is open
(1) One outdoor unit installed individually
(2) Two or more units installed side by side
*
a
a 500 mm or more
a
c
b
a 1,000 mm or more
b 250 mm or more
c 250 mm or more
* When also using the air-discharge chamber, provide a space
of 500 mm or more.
When an obstruction is present also in the upward area
(1) One outdoor unit installed individually
(2) Two or more units installed side by side
a
c
b
a 500 mm or more
b 500 mm or less
c 300 mm or more
a
c
b
e
d
a 500 mm or more
b 250 mm or more
c 250 mm or more
d 500 mm or less
e 1,000 mm or more
(C) When an obstruction is present on both the air inlet and air outlet sides
Case 1: When an obstruction on the air outlet side is higher than the outdoor unit (L > H)
(There is no height restriction on the air inlet side.)
When the upward area is open
(1) One outdoor unit installed individually
(2) Two or more units installed side
by side
a
b
d
c
H
L
a 200 mm or more
b 1,000 mm or more
c 250 mm or more
d 250 mm or more
*
a
b
H
L
a 100 mm or more
b 500 mm or more
When an obstruction is present also in the upward area
(1) One outdoor unit installed individually
a
A
c
L
H
b
a 200 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
L
A
L
≤
H
0 < L
≤
1/2H
300
1/2H < L
≤
H
500
H < L
Install the frame to achieve L
≤
H.
Close the area under the frame so that the outlet air does
not bypass there.
(2) Only two outdoor units installed side by side
b
a
A
c
L
H
a 200 mm or more
b 500 mm or less
c 1,000 mm or more
The dimensional relationship between H, A, and L is as
shown in the following table.
Unit: mm
L
A
L
≤
H
0 < L
≤
1/2H
500
1/2H < L
≤
H
750
H < L
Install the frame to achieve L
≤
H.
Close the area under the frame so that the outlet air does
not bypass there.
Only two outdoor units can be installed side by side.
SM830283-00_欧州向け R32シングル36-71形TD&SM.indb 13
20/01/30 10:26:01
Summary of Contents for S-3650PF3E
Page 20: ...19 MEMO SM830283 00_欧州向け R32シングル36 71形TD SM indb 19 2020 01 29 21 46 03 ...
Page 178: ... MEMO 1 13 5 SM830283 00_欧州向け R32シングル36 71形TD SM indb 5 20 01 30 10 26 09 ...
Page 198: ... MEMO 2 4 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 19 52 20 ...
Page 204: ... MEMO 3 2 1 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 20 01 28 11 25 46 ...
Page 270: ... MEMO 5 4 3 SM830283 00_欧州向け R32シングル36 71形TD SM indb 3 2020 01 29 21 17 57 ...
Page 272: ... MEMO 6 1 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 20 10 15 08 ...
Page 294: ... MEMO 7 21 SM830283 00_欧州向け R32シングル36 71形TD SM indb 21 20 01 28 11 22 25 ...
Page 321: ...202001 SM830283 00_欧州向け R32シングル36 71形TD SM indb 1 20 01 23 9 32 11 ...