No. SX-DSV02829 -
155-
Error No.
Protective function
Causes
Measures
Maiin
Sub
81
7
SyncManager2/3
error protection
A setup of SyncManager2/3 was set as the unjust value.
- A Physical Start Address (ESC registersh 0810h) setting of
SyncManager2 is inaccurate.
- The area for reception overlaps the area for
transmission.
- The area for transmission/reception of Mailbox
overlaps the area for transmission/reception of
SyncManager2/3
- Address specification of the area for
transmission/reception is odd number.
- The start address is out of range.
- A Length (ESC registersh 0812h) setting of SyncManager2
is inaccurate.
- Different from RxPDO size.
- A Control Register:ESC register (0814h) setting of
SyncManager2 is inaccurate.
- Other than 100100b is set for bit5-0.
- A Physical Start Address (ESC registersh 0818h ) setting of
SyncManager3 is inaccurate.
- The area for reception overlaps the area for
transmission.
- The area for transmission/reception of Mailbox
overlaps the area for transmission/reception of
SyncManager2/3
- Address specification of the area for transmission/
reception is odd number.
- The start address is out of range.
- A Length (ESC register 081Ah) setting of
SyncManager3 is inaccurate.
- Different from TxPDO size.
- A Control Register:ESC register (081Ch) setting
of SyncManager3 is inaccurate.
- Other than 100000b is set for bit5-0.
- Set up SyncManager2/3 correctly.
84
3
Synchronous
establishment
initialization
error protection
Error occurred during communication and servo sync and
initialization process.
• Turn off the power once, then re-enter.
• If error repeats, this might be a failure.
Stop using the products, and replace the motor and the
driver.
• Return the products to the dealer or manufacturer.
(To be continued)
R1.00
Motor Business Unit, Panasonic Corporation