Chapter 3 Function
3-3
3
Class
Function
Details
Initial value
Memory
change*
Ref.
page
Judgment Output
Selection
Sets the operation of the output block.
Default: 2-state
3-22
Threshold a
Threshold b
Sets threshold a
and threshold b.
Default: +(detection range)
Default: -(detection range)
Displace
ment
Judgment Hysteresis
Sets the hysteresis.
Default: +(0.2% of setting range)
3-24
Judgment Output OFF
Delay
Delays the timing of judgment output switched OFF
from ON.
Default: OFF
3-25
Out
put
S
et
ting
s
Measurement Value
Display on Panel
Turns OFF the rightmost digits on the digital display.
Default: SET 1
3-27
Analog Output
Selection
Selects the desired output type from current output and
voltage output.
Default: Current output
3-28
Meas A
Default: Negative measurement range
Current A
Default: +4.000 mA
Voltage a
Default: 0.000 V
Meas B
Default: Positive measurement range
Current B
Default: +20.000 mA
An
al
og
Se
tti
ngs
Analog
Scaling
Voltage b
Performs scaling
the analog current
output and the
analog voltage
output to any
desired value.
Default: 10.000 V
3-29
Analog Output at Alarm
Sets the analog output status at alarm operation.
Default: Holds previous value
3-31
Digital Output at Alarm
Sets the digital output status at alarm operation.
Default: Holds previous value
3-32
Al
ar
m Set
tin
gs
Alarm Delay Times
Holds the previous normal value up to the setting
number of times if an alarm is issued.
Default: 8 times
3-33
Terminating Resistor
Selection
Selects the terminating resistor for the sensor head
connecting to the host device over RS-422/485.
Default: R3
3-34
Sensor no.
Sets the number of each sensor head multi connected
to an RS-485 device.
Default: 01
3-35
Baud rate
Sets the communication speed.
Default: 38400 bps
3-36
Connection Mode
Selects the performance settings for measurement data
output to the host device.
Default: RS-485 Multiple
3-37
C
O
M
S
ettings
Sending Delay Time
Set the sensor's delay time in response to each
command transmitted from the host device.
Default: 0ms
3-38
Timing Mode
Sets the timing input mode.
Default: Hold
3-39
Laser Control
Switches laser emission/stop.
Default: Emission
3-40
Eco Mode
Turns OFF the LED indicators on the control panel for
energy saving while the system is in RUN mode.
Default: Eco OFF
3-41
View Version
Displays the program version of the sensor.
-
3-42
Initialization
Initializes the memory settings currently in use.
3-43
Save
Saves all memory settings.
3-44
Sy
st
em
S
ettin
gs
Timing
Holds the measurement value.
Default: OFF
3-45
Summary of Contents for HL-G1 A-C5 Series
Page 18: ...Introduction 16 ...
Page 151: ......