6-33
6.8.4 Interface Specifications (GT21)
Interface for connecting PLC/External devices
- COM port
Item
Specifications
AIGT2230B/AIGT2230H
AIGT2232B/AIGT2232H
Communication standard
Conforms to RS232C
(Non insulation type)
Conforms to RS422
(Non insulation type)
Communication
condition with
external
devices
Baud rate (bit/s) 9600, 19200, 38400, 57600, 115200 bps
Data length (bit) 7, 8
Parity
None, Odd, Even
Stop bit (bit)
1
Transmission distance
(Total length)
Max. 15 m
(Baud rate: 19200 bit/s)
Max. 500 m
(Baud rate: 115200 bit/s)
Protocol
-
MEWTOCOL (Protocol for PANASONIC PLC: FP series)
-
General-purpose serial (PANASONIC dedicated protocol)
-
Other companies' PLC protocols (For the details, refer to the latest
GTWIN HELP.)
Connector
Connector terminal base (8-pin)
Note1) 2)
Note1) The (+) and (-) terminals are the power supply terminals for driving the main unit.
Note2) Regarding power supply voltage, please pay due consideration to the cable length so that the
applied voltage is within the operation voltage range.
Interface for transferring screen data
- TOOL port
Item
Specifications
Communication standard
Conforms to RS232C (Non insulation type)
Conditions for
communications
with GTWIN
Baud rate (bit/s) 9600, 19200, 115200, 230400 bps
Note1) 2)
Data length (bit) 8
Parity
None, Odd, Even
Stop bit (bit)
1
Protocol
GT dedicated protocol
Connector
Mini-DIN (5-pin)
Note1) The baud rate of 230400 bps is available when the USB/RS232C conversion cable is used.
Note2) When the baud rate is set to 230400 bps, the connection using the GTWIN automatic
communication setting function is not possible. Set the GTWIN communication setting to 230400
bps, and then transfer data.
Summary of Contents for GT32-R
Page 25: ...Chapter 1 Features and Functions ...
Page 40: ...1 16 ...
Page 41: ...Chapter 2 Names and Functions of Parts ...
Page 42: ...2 2 2 1 Part Names 2 1 1 GT01 GT11 GT21 GT01 GT01R GT11 GT21 ...
Page 44: ...2 4 2 1 2 GT02 GT02L GT02M2 GT02G2 GT02M0 GT02M1 GT02G0 GT02G1 GT02L ...
Page 48: ...2 8 2 1 4 GT05 GT12 GT32 GT32 R GT32 E GT05 GT12 GT32 Standard High function ...
Page 49: ...2 9 GT32 R GT32 E ...
Page 62: ...2 22 ...
Page 63: ...Chapter 3 Installation and Wiring ...
Page 86: ...3 24 ...
Page 87: ...Chapter 4 Connecting with PLC ...
Page 122: ...4 36 ...
Page 123: ...Chapter 5 Troubleshooting ...
Page 141: ...Chapter 6 Specifications ...
Page 187: ...Chapter 7 Dimensions and Other Documentation ...
Page 188: ...7 2 7 1 Dimensions 7 1 1 GT01 GT01R Installation dimensions Panel cutout dimensions ...
Page 189: ...7 3 7 1 2 GT02 Installation dimensions Panel cutout dimensions ...
Page 190: ...7 4 7 1 3 GT02L Installation dimensions Panel cutout dimensions ...
Page 191: ...7 5 7 1 4 GT03M E Installation dimensions Panel cutout dimensions ...
Page 193: ...7 7 7 1 6 GT05 Installation dimensions Panel cutout dimensions ...
Page 194: ...7 8 7 1 7 GT11 Installation dimensions Panel cutout dimensions ...
Page 195: ...7 9 7 1 8 GT12 Installation dimensions Panel cutout dimensions ...
Page 196: ...7 10 7 1 9 GT21 Installation dimensions Panel cutout dimensions ...
Page 198: ...7 12 7 1 11 GT32 R GT32 E Installation dimensions Panel cutout dimensions ...
Page 200: ...7 14 7 2 4 AIGT8175 7 2 5 AIP81842 ...
Page 202: ...7 16 7 4 ASCII Code Table ...
Page 205: ......