6-6
6.2 GT02
6.2.1 General Specifications (GT02)
Item
Specifications
24 V DC type
5 V DC
Rated voltage
24 V DC
5 V DC
Operating voltage range
21.6 to 26.4 V DC
4.5 to 5.5 V DC
Power consumption
1.9 W or less (80 mA or less)
1W or less
(200 mA or less)
Note1)
Ambient temperature
0 to +50
C
Ambient humidity
20 to 85% RH (at 25
C), non-condensing
Storage temperature
-20 to +60
C
Storage humidity
10 to 85% RH (at 25
C), non-condensing
Breakdown voltage
Between [power supply terminals] and [case]
500 V AC for 1 minute, Cutoff current 10mA (at default setting)
Insulation resistance
Between [power supply terminals] and [case]
100 M
or more, 500 V DC, measured with megohmmeter (at default
setting)
Vibration resistance
5 to 8.4 Hz half amplitude 3.5 mm,
8.4 to 150 Hz acceleration 9.8 m/s
2
,
10 sweeps each in X, Y and Z directions (1 octave/min)
Shock resistance
147 m/s
2
, 3 times on 3 axes
EC Directive applicable
EN61131-2 (EMC Directive)
Noise immunity
1000 V [P-P] or more, Pulse width 50 ns, 1
s between power supply
terminals (based on in-house measurements)
Note2)
Protective construction
IP67 (Initial value, evaluated by us)
Dustproof and drip-proof from front panel only (packing used on panel
contact surface)
Note3)
Weight
Approx. 170 g
Note1) When supplying the power from the TOOL port of a PLC (CPU unit), confirm the PLC restrictions
such as the power supply capacity before use.
Note2) When using our exclusive cable.
Note3) When reattaching, replace waterproof packing.
Summary of Contents for GT32-R
Page 25: ...Chapter 1 Features and Functions ...
Page 40: ...1 16 ...
Page 41: ...Chapter 2 Names and Functions of Parts ...
Page 42: ...2 2 2 1 Part Names 2 1 1 GT01 GT11 GT21 GT01 GT01R GT11 GT21 ...
Page 44: ...2 4 2 1 2 GT02 GT02L GT02M2 GT02G2 GT02M0 GT02M1 GT02G0 GT02G1 GT02L ...
Page 48: ...2 8 2 1 4 GT05 GT12 GT32 GT32 R GT32 E GT05 GT12 GT32 Standard High function ...
Page 49: ...2 9 GT32 R GT32 E ...
Page 62: ...2 22 ...
Page 63: ...Chapter 3 Installation and Wiring ...
Page 86: ...3 24 ...
Page 87: ...Chapter 4 Connecting with PLC ...
Page 122: ...4 36 ...
Page 123: ...Chapter 5 Troubleshooting ...
Page 141: ...Chapter 6 Specifications ...
Page 187: ...Chapter 7 Dimensions and Other Documentation ...
Page 188: ...7 2 7 1 Dimensions 7 1 1 GT01 GT01R Installation dimensions Panel cutout dimensions ...
Page 189: ...7 3 7 1 2 GT02 Installation dimensions Panel cutout dimensions ...
Page 190: ...7 4 7 1 3 GT02L Installation dimensions Panel cutout dimensions ...
Page 191: ...7 5 7 1 4 GT03M E Installation dimensions Panel cutout dimensions ...
Page 193: ...7 7 7 1 6 GT05 Installation dimensions Panel cutout dimensions ...
Page 194: ...7 8 7 1 7 GT11 Installation dimensions Panel cutout dimensions ...
Page 195: ...7 9 7 1 8 GT12 Installation dimensions Panel cutout dimensions ...
Page 196: ...7 10 7 1 9 GT21 Installation dimensions Panel cutout dimensions ...
Page 198: ...7 12 7 1 11 GT32 R GT32 E Installation dimensions Panel cutout dimensions ...
Page 200: ...7 14 7 2 4 AIGT8175 7 2 5 AIP81842 ...
Page 202: ...7 16 7 4 ASCII Code Table ...
Page 205: ......