operation procedure

 

If you change settings, press the SET key before you turn the power 
OFF. Otherwise your changes will be lost.

 

● With FX-502□, press the MODE key for 3 seconds to switch from 

sensing output 1 to sensing output 2.

When you turn the power ON, the amplifier is in RUN mode. Press the 

MODE key (indicated by black arrow in the illustrations below) to switch 
from one mode to the next.

RUN mode

 

Displays the threshold value in green 
and the incident light intensity in red.

 

● Used for teaching, making fine 

adjustments to the threshold values 
(see page 5), and activating the 
key lock function (see page 5).

Sensing output operation mode

 

Select either Light‑ON or Dark‑ON. 
The default setting is 

 (Light‑ON).

 

Refer to sensing output operation 
mode on page 5 for details.

CUSTOM mode

 

Displays one of the three settings 
available in CUSTOM mode (re‑
sponse time, emission power, hyster‑
esis). The default setting is 
(response time).

 

Refer to CUSTOM mode on page 
5 for details.

PRO mode

 

Used for advanced settings.

 

Refer to PRO mode on page 6 
for details.

RUN mode

7

teaching

 

Please note that if the threshold values are very close to each other, 
objects may not be detected reliably.

 

For teaching in Window Comparator mode or Hysteresis mode, 

you need to set the shift amount in PRO mode first. For the setting 

procedure, refer to the “PRO MODE OPERATION MANUAL” (only 
available in English). 

 

If you use 1‑point teaching, set the shift amount (the initial value is 
10% or 100) in PRO mode.

Teaching is performed in RUN mode. There are different teaching methods 
available. Which teaching method is recommended depends on the sensor 
type and whether the sensing object is present or not present or moving.

sensing condition

recommended teaching 
method

Sensing object is present and easily 
detectable.

2‑point teaching

Sensing object is very small.

Other objects are in the background.

Limit teaching

Production line cannot be stopped and 
sensing object is moving

Auto teaching

All teaching methods are available for the thru-beam and the reflective type.

2-point teaching

The basic teaching method when the sensing object is present is 

2-point 

teaching

.

Thru-beam type

Reflective type

1. 

2. 

1. 

2. 

1.  Press the SET key when the sensing 

object is present.

2.  Press the SET key when the sensing 

object is absent.

Display when stable sensing is possible.

Display when stable sensing is not possible. 

limit teaching

When the sensing object is small or there are objects in the background, 

use this teaching method. Both the thru-beam type and the reflective type 

can be used. The procedure only shows the thru‑beam type.

Sensing object is present

Sensing object is not present

1.  Press the SET key 

when the sensing 
object is present or 
not present.

2.  Press the UP key to 

shift the threshold 
level to a high level 
(low sensitivity) or 
press the DOWN key 
to shift the threshold 
level to a low level 
(high sensitivity).

Display when stable sens‑
ing is possible.

Display when stable sens‑
ing is not possible.

Full auto teaching

When the sensing object is moving, use this 
teaching method. Both the thru‑beam type 

and the reflective type can be used. The pro

cedure only shows the thru‑beam type.

1.  Press and hold the SET key for a long time

2.  Run the sensing object on the production 

line and hold down the SET key.

3.  The display shows 

 in green. When 

the sensing object has passed through, 
release the SET key.

Summary of Contents for FX-501 Series

Page 1: ...tput is active Yellow Sensing output is selected Orange Sensing output is operating 2 Sensing output 2 lit if output is active Yellow Sensing output is selected Orange Sensing output is operating 3 Digital display green red 4 UP key Functions Teach Fine adjustment of the threshold value Select settings 5 DOWN key 6 MODE key Functions Select modes Cancel 7 SET key Functions Teach Confirm selected s...

Page 2: ...e 5 I O circuit diagrams FX 501 NPN type 12 24V DC 10 15 Main circuit Brown V see note Load Black sensing output Blue 0V see note FX 501P PNP type 12 to 24V DC 10 15 Main circuit Brown V see note Load Black sensing output Blue 0V see note The quick connection sub cable does not have V brown and 0V blue The power is supplied from the connector of the main cable Terminal arrangement 1 2 3 Terminal n...

Page 3: ...mmended depends on the sensor type and whether the sensing object is present or not present or moving Sensing condition Recommended teaching method Sensing object is present and easily detectable 2 point teaching Sensing object is very small Other objects are in the background Limit teaching Production line cannot be stopped and sensing object is moving Auto teaching All teaching methods are avail...

Page 4: ...SL P 1 2_SL P 2 1_SL P 1 2_SL P 2 1_SL P 1 Teaching point 1 serving as the lower threshold value 2_SL P 2 Teaching point 2 serving as the upper threshold value 1 Press the SET key when the first sensing object is present 2 Press the SET key again when the second sensing object is present Display when stable sensing is possible Display when stable sensing is not possible If you select a value excee...

Page 5: ... shows Activating the key lock function 1 Press the SET and the MODE key together for 3 seconds or longer The digital display changes to show the key lock function has been activated Then the digital display returns to show the current values Deactivating the key lock function 1 Press the SET and the MODE key together for 3 seconds or longer The digital display changes to show the key lock functio...

Page 6: ... sensor amplifiers pressure sensor controllers etc install the prod ucts so that they are in order of group A B D and C as shown in the figure below This product is included in group D Within each group identical models should be mounted next to each other Communication direction Group A Group B Group D Group C Group Model number A FX 301 conventional version unit FX 301B G H LS 401 B FX 301 modif...

Page 7: ... gap be tween the master communication unit and the subordinated amplifiers 16 Cautions This product has been developed produced for industrial use only This product is suitable for indoor use only Make sure to add or remove amplifiers with the power OFF If you apply a voltage exceeding the rated range or if an AC power supply is connected directly the product may get burnt or damaged Shortcircuit...

Page 8: ... SP FAST STD 0 to 4 000 display in LONG 0 to 8 000 see note 4 Response time 2ms or less Zero point within 4mA 1 F S Span within 16mA 5 F S Linearity within 3 F S Load resistance 0 to 250Ω External input switchable with output 2 for FX 502 Signal condition of NPN non contact input High 8V to V DC or Open Low 0 to 1 2V DC at 0 5mA source current Input impedance Approx 10kΩ Signal condition of PNP no...

Reviews: