Technical/Programming Manual
FT1020G3 Rev 2.2.1
86
The types that can be used in the "Output signal period" for the programmable output
respectively are:
X
= Output type that can be used.
XX
= Output type that can be used but only 0.8s/0.8s.
XXX
= Output type that can be used but max. 5.6s/5.6s and the pulse max. 5.6s
respectively.
13.5
Control expression
Each programmable output has to be given a control expression
95
. It is created using
Boolean algebra.
If an output is to be used for manual control only e.g. an AS1668 fan control output or an
output controlled by input trigger condition “Activate output”, a “never true” control
expression
must
be
programmed.
In
such
a
case,
control
expression
“TimeChannelActivated” (Always off) can be used.
Trigger conditions (see "Available functions"), logical "Operators" (
AND
,
OR, NOT
) and
parentheses are used to build up a "control expression" containing up to 40 trigger
conditions. See also chapter "Control expression examples" page 92.
A programmable output will be activated as long as its control expression is true.
Figure 32 EBLWin control expression
In any output dialog box, click the right mouse button in the large white field. Select Alarm,
Interlocking, Disablement or Other to open a “Trigger condition list”. Depending on the
selected trigger condition, different arguments / data have to be entered. In Figure 32, the
trigger condition "General Fire Alarm) is selected.
13.5.1
Trigger conditions
Some trigger conditions require additional information, see below information within
parentheses (+nnnnn) after the trigger condition respectively.
The trigger conditions are divided into four groups as follows:
Alarm
Interlocking
95
A programmable output with no control expression will be interpreted by the CIE. as if it does not exist.