Technical/Programming Manual
FT1020G3 Rev 2.2.1
25
Table 3 Expansion boards address (jumpers) setting
Board no.
(address)
4580, 4581 and 4583
4582
JP2
JP3
JP4
JP1
JP2
JP3
0
1
X
X
2
X
X
3
X
X
X
X
4
X
X
5
X
X
X
X
6
7
X=Shunted, Blank = Open
Address 6 & 7 are not currently used
5.1
8 zones expansion board 4580
Each board has to be programmed via EBLWin with an address (Board no.) which is set
via the jumpers "JP2-JP4", see Table 3 above.
The 4580 board has eight conventional zone line inputs (0-7) intended for conventional
detectors, MCP, flow switch input or any N/O clean contact. The end-of line device must
be connected in the last alarm point on each zone, depending on the selected "Type of
zone line input", see below.
Connections to "J1:1-16" and "J2" according to drawing F728.
Each zone line input has to be programmed via EBLWin for the following:
Type of zone line input (see below), depending on detectors / end-of-line device
(capacitor or resistor), i.e. different threshold levels etc.
Alarm at short circuit i.e. whether a short- circuit on the zone line input generates
a fault or a fire alarm.
Zone number (address optional)
AVF (Alarm Verification Facility), if required
Text (Alarm / fault text when required)
Alert annunciation time channel
Disable time channel
Two-unit dependency time channel
Type of detectors connected to the zon
e line input (see “Fire alarm type A and Fire
” page 118 for an explanation of A and B)
The terminals support a wire size up to 1.13 mm
2
(1.2 mm).
5.1.1
Type of zone line input
Each input must be selected either as
”
Not used
”
or as one of the following types / modes.