Units connected to the RS232 interface J7
9.3.1
Web-servers
1598
Web-server II. This unit can be used in the following applications:
a)
For presentation of the actual CIE status on a PC using a web browser such
as Microsoft Internet Explorer. It can also send e-mails in case of pre-warning,
fire alarm, fault, disablement and test mode alarm and/or service signal.
b)
For remote control via two-way communication. Up to 10 User names with an
individual Password
75
and three different access levels.
c)
As a gateway to other PC systems etc.:
c1) EBL Talk (RS232 or TCP/IP) is an open protocol, used to transmit and
present fire alarm information in a separate PC / system.
c2) Tateco (RS232) used to transmit and present fire alarm information in an
Ascom Tateco paging system.
c3) SIA (RS232) used to transmit and present fire alarm information in a
separate PC application.
c4) MODBUS (RS232)
used to transmit and present fire alarm
information in a separate PC application.
d)
As a gateway to a security management system via EBLnet. (TCP/IP) EBLnet
licence required.
The Web-Server has to be preconfigured with proper TCP/IP protocols using
@CHIPTOOL before setting up the Web-Server SSD configuration in the PC
program EBLWin. The Web-Server SSD configuration is downloaded to the Web-
Server via TCP/IP using an Ethernet cable. The Web-Server software is also
downloaded via the PC program EBLWin.
The Web-server II consists of a light grey plastic enclosure (90x25x69.5 mm),
which can be mounted on a 35 mm DIN rail inside the FT1020G3 CIE
Web-server II has the following interfaces:
RS232
(PLC COM) to connect the web-server to J7 in the FT1020G3 CIE
RS232
(MODEM COM) to connect the web-server to other PC / system
RJ45
(10 BASE-T) to connect the web-server to Internet / an intranet (LAN)
Molex 3.5
to connect the web-server to J3 (24 V
DC
) in the FT1020G3 CIE
Details for setting up the Web-Server is found in MA440 Web Server II Manual Rev
1.0 for FT1020G3 and FT128.
9.4
Other units
9.4.1
External LEDs
BARIL
Remote Indicator RIL. Used when a detector is placed out of view or hidden e.g.
roof space detectors. The LED is lit at the same time as the LED in the detector /
base that is connected to. It has a "Burning house" symbol instead of any text.
BARIL can be connected to all types of Panasonic detectors / bases. The input is
polarised.
J2:1 (+5 to +35 V
DC
) for
Conventional
detectors / bases
J2:2 (< 25 mA) for
Analogue
detectors / bases
J2:3 (0 V)
To be wall mounted (87 x 87 x 39 mm)
75
Consists of 6 digits.