Technical/Programming Manual
FT1020G3 Rev 2.2.1
120
17.16.1
Disable / Re-enable zone
A whole zone (all addressable alarm points within a zone, including the manual call points)
can be disabled via menu H2/B1 or via the zone control front buttons (if fitted). This menu
is also used to disable a conventional zone, i.e. a 3361 unit's zone line input (Z) and
expansion board 4580 zone line inputs. Re-enable via menu H2/B4 or automatic re-
enabling at a specified time.
17.16.2
Disable / Re-enable zone - address
Individual alarm points (zone-address) can be disabled and re-enabled via menu H2/B1.
A time channels can instead be used to disable and re-enable automatically.Disable / Re-
enable control output
All outputs (except outputs of type "Alarm Device") can be individually disabled and re-
enabled via menu H2/B2. Disabled output will stay in (or return to) the normal condition for
the output respectively.
17.16.3
Disable / Re-enable output type
The control outputs can be collectively disabled via menu H2/B3, type:
"Control (general)"
"Extinguishing"
"Ventilation"
"Interlocking"
It is possible to do this for one or more specific Control Units or for all Control Units (i.e. the
whole system). Re-enabled via menu H2/B3. Disabled outputs will stay in (or return to) the
normal condition for the output respectively.
17.16.4
Disable / Re-enable alarm devices
The control outputs of type "Alarm device
” (OWS) can be collectively disabled via menu
H2/B4. It is only possible to do this for all Control Units (i.e. the entire system). Disabled
outputs will stay in (or return to) the normal condition for the output respectively.
17.16.5
Disable / Re-enable interlocking output
The
type “Interlocking output” can be individually disabled and re-enabled via menu H9/C3.
See also chapter "Disable / re-enable interlocking output (H9/C3)", page 100.
17.16.6
Disable / Re-enable outputs for routing equipment
The control outputs of type "Routing equipment (Fire brigade TX and Fault TX)" can be
Disabled and Re-enabled via menu H2/B5. For more information see FT1020G3 Operation
Manual.
17.16.7
Disable / Re-enable alert annunciation function
The alert annunciation function can be disabled / re-enabled via menu H2/B6. Disabled
alert annunciation function will be disabled until Re-enabled. Refer to FT1020G3 Operation
Manual.
17.16.8
Disconnect & Re-connect loop / zone line input
The following can be d
isconnected and re-connected via menu H8/S1:
COM loop