background image

Description

The NBG-12 Series Pull Stations are non-coded manual pull
stations which provide a Fire Alarm Control Panel (FACP)
with a single alarm initiating input signal.  The NBG-12
series includes both single-action and dual-action models
equipped with either a hex or key lock / reset.  A single-action
pull-station is activated by a single pull-down of the alarm
handle.  The dual-action versions require pushing in the
handle, then pulling the handle down for activation.  The
NBG-12 series manual pull stations are UL listed and meet the
ADA requirement of a 5-lb. maximum pull force to activate.
Operating instructions are molded into the handle along with
Braille text.  Molded terminal numbers can be found adjacent
to the wiring terminals.

 Document: 51015   Revision: B2   ECN: 03-126   03/13/03

US Patents D428,351; 6,314,772; 6,380,846

NBG-12 Series Models available:

NBG-12S

 – Single action with ‘pigtail’ connections and

a hex lock reset.  Pigtail wires are provided for connec-
tion to the Fire Alarm Control Panel’s (FACP) Initiating
Device Circuit (IDC).

NBG-12 

– Dual action model with screw terminal

connections and a hex lock reset.

NBG-12L

 – Same as NBG-12 except with a key lock reset.

NBG-12LSP

 – Same as NBG-12L except with both

English and Spanish operating instructions.

NBG-12 Series Manual Pull Stations

Installation

Surface mount the NBG-12 pull station to a SB-10 surface backbox.
Semi-flush mount the NBG-12 to a standard single gang, double-
gang, or 4-inch (10.16 cm) square electrical box.  Mount the
optional Trim Ring (BG-TR) if necessary when semi-flush mounting
the unit.

Dual Action NBG-12L

Switch Contact Rating

All switch contacts are rated for 0.25 A at 30 volts (AC or DC).

The word ‘ACTIVATED’

is displayed

on the pull station’s
pulled-down handle

P/N 50997  REV.

REFER TO DOCUMENT

NUMBER 51015 REV.

LOOP

ADDRESS

10

11

12

13

P/N 50997  REV.

REFER TO DOCUMENT
NUMBER 51015 REV.

LOOP

ADDRESS

10

11

12

13

14

9

C

B

A

POST

DOOR ‘KEYS’ INTO

BACKPLATE AT THIS POINT

POST

POST

HOLE

HOLE

DOOR MATED TO BACKPLATE

With the door and
backplate aligned and
‘keyed’ together, slide
the holes down onto
the posts.

Closing the door slightly
locks the door and
backplate together.

NBG12-Face2.cdr

If, during mounting of the pull station, the door becomes de-
tached

, complete the following steps to reattach the door to the

backplate.  The door cannot be connected to the pull station if the
unit is mounted to the backbox.
1. Position the door and backplate side by side in the full open

position.  (i.e. 180 degrees with respect to each other.)

2. With the backplate position fixed, move the door behind the

backplate, as shown in the illustration, part A.

3. Align the hinge posts and holes by bringing the door up to meet

the backplate,  paying particular attention to the ‘keying’ that
occurs when the door’s post hole is aligned to the backplate’s
hinge post.  Refer to the illustration, part B.

4. With the two pieces aligned and ‘keyed’ together, slide the holes

down onto the posts.  Refer to the illustration, part C.

5.

Holding the backplate, close the door slightly to lock the door
and backplate together.

DOOR ATTACHMENT

www.PDF-Zoo.com

Reviews: