background image

 

 

_______________________________________________________________________________________________________________________________ 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                            www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D202-00-211-IS 

Issue 4        16-12-2022                         Sheet 1 of 7

 

                                                               

 
 

1)  WARNING: 

 USE COVER BOLTS CLASS A4-70 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 POTENTIAL ELECTROSTATIC HAZARD 

 FOR INDOOR OR OUTDOOR USE 

 TO REDUCE THE RISK OF IGNITION OF 

HAZARDOUS ATMOSPHERES, CONDUIT 
RUNS MUST HAVE A SEALING FITTING 
CONNECTED WITHIN 18 INCHES OF 
CONDUIT 

 

CAUTION - RISK OF ELECTRIC SHOCK - 
MORE THAN ONE DISCONNECT MAY BE 
REQUIREDTO DE-ENERGIZE THE 
EQUIPMENT BEFORE SERVICING

 

 

AVERTISSEMENT: 

 

UTILISER COUVRIR BOULONS CLASSE A4-

70 

 

NE PAS OUVRIR UN PRESENCE 

D'ATMOSPHERE EXPLOSIVE 

 

DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE -  VOIR LES 

INSTRUCTIONS 

 

POUR USAGE INTÉRIEUR OU EXTERIEUR 

 

POUR RÉDUIRE LE RISQUE 

D'INFLAMMATION DES ATMOSPHÈRES 

DANGEREUSES, LES CONDUITES DE 

CONDUIT DOIVENT AVOIR UN RACCORD 

D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18 

POUCES DE L'ENFERMEMENT 

 

ATTENTION - RISQUE DE CHOC 

ELECTRIQUE - PLUSIEURS SECTIONNEURS 

PEUVENT ETRE NECESSAIRES POUR 

COUPER L'ALIMENTATION DE 

L'APPAREILLAGE AVANT 

D'ENTREPRENDRE L'ENTRETIEN 

 

2)  Rating & Marking Information 

 

2.1 NEC & CEC Class / Division Ratings for US / Canada 

 

The GNExCP7 callpoints comply with the following 
standards:  

 

UL 60947-4-1 Low voltage switchgear and controlgear – Part 4-1: 
Contactors and motorstarters – Electromechanical contactors and 
motorstarters – Ed. 3 Rev. date 2017/10/ 

 

CSA C22.2 NO. 60947-4-1-14 Low voltage switchgear and 
controlgear – Part 4-1: Contactors and motorstarters – 
Electromechanical contactors and motorstarters – Ed. 2 - Issue Date 
2014/01/04 

 

 
 

 
The GNExCP7 callpoints are rated as follows:  

 

Class I Div 2  Group ABCD T6  Ta -55°C to +60°C 
Class II Div 2  Group FG T4  Ta -55°C to +60°C 
Class III Div 1 & 2  Ta -55°C

 

to +60°C 

 

2.2 NEC Class / Zone ratings US 

 
The GNExCP7 callpoints comply with the following 
standards:  

 

UL 60079-0:2017 (Ed 6): Explosive Atmospheres - Part 0: Equipment 
- General requirements  
UL 60079-1:2015 (Ed7): Explosive Atmospheres - Part 1: Equipment 
protection by flameproof enclosures “d” 
UL 60079-31:2012 (Ed 2): Explosive Atmospheres - Part 31: 
Equipment dust ignition protection by enclosure "t" 

 

The GNExCP7 callpoints are rated as follows:  

 

Class I Zone 1 AEx db IIC T6 Gb (Ta -55°C to +60°C) 
Zone 21 AEx tb IIIC T125°C Db (Ta -55°C to +60°C) 

 
2.3 CEC Class / Zone ratings Canada 

 

The GNExCP7 callpoints comply with the following 
standards:  

 

CSA C22.2 NO. 60079-0:2015 (Ed 3) Explosive Atmospheres – Part 
0: Equipment – General requirements  
CSA C22.2 NO. 60079-1:2016 (Ed 3): Explosive Atmospheres – Part 
1: Equipment protection by flameproof enclosures “d” 
CSA C22.2 NO. 60079-31:2015 (Ed 2): Explosive Atmospheres – 
Part 31: Equipment dust ignition protection by enclosure “t” 

 

The GNExCP7 callpoints are rated as follows:  

 

Class I Zone 1 Ex db IIC T6 Gb X (Ta -55°C to +60°C) 
Zone 21 Ex tb IIIC T125°C Db (Ta -55°C to +60°C) 

 

2.4 ATEX / IECEx / UKEX Certification 

 
The GNExCP7 callpoints comply with the following 
standards:  
 

EN60079-0:2018 / IEC60079-0:2017 (Ed 7): Explosive Atmospheres 
– Part 0: Equipment. General requirements 
EN60079-1:2014 / IEC60079-1:2014 (Ed 7): Explosive Atmospheres 
- Part 1: Equipment protection by flameproof enclosures "d" 
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): Explosive 
Atmospheres - Part 31: Equipment dust ignition protection by 
enclosure "t" 

INSTRUCTION MANUAL  

GNExCP7-PB-S, GNExCP7-PB-D, GNExCP7-PM-S, GNExCP7-PM-D, 

GNExCP7-PT-S & GNExCP7-PT-D CALL POINTS 

For use in Flammable Gas Atmospheres 

Summary of Contents for GNExCP7-PB-D

Page 1: ...s Electromechanical contactors and motorstarters Ed 2 Issue Date 2014 01 04 The GNExCP7 callpoints are rated as follows Class I Div 2 Group ABCD T6 Ta 55 C to 60 C Class II Div 2 Group FG T4 Ta 55 C t...

Page 2: ...it will only exist for a short time Dust Groupings Group IIIA Combustible Flyings Group IIIB Non conductive Dust Group IIIC Conductive Dust Maximum Surface Temperature for Dust Applications ATEx IECE...

Page 3: ...re between the two castings is secure and the O ring seal is in place When fitting the flameproof cover ensure the cover is sitting flat and correctly positioned on the base Insert the M6 x 50 stainle...

Page 4: ...Ex UKEX certified adapters 10 Cable Connections Electrical Connections are to be made into the terminal blocks using solid or stranded wire See section 6 of this manual for access to the flameproof en...

Page 5: ...y twisted by 90 degrees clockwise to position shown and then pressed in There will be a click sound to indicate positive engagement and the plunger will stay in place Fig 6 PB Version Twist and Push A...

Page 6: ...ximum voltage stated must not be exceeded as the internal resistor modules are rated as compliant with Ex d according to the unit voltage If lower value resistors than seen on table are required it ma...

Page 7: ...idered suitable for use in low demand safety function Random Hardware Failures and Systematic Failures route 2H As an unvoted item i e hardware fault tolerance of 0 at SIL 2 The product was assessed a...

Page 8: ...as shown in Operated condition Terminals 4 5 7 8 closed Terminals 4 5 6 open COM N O N C EOL SER NOTE These can be fitted either by customer or pre installed by E2S at point of order When fitting diod...

Page 9: ...1 2 3 4 5 6 7 8 COM N O N C COM N O N C COM N O N C COM N O N C Standard Unit showing positions of optional Series and EOL Devices 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM 4A Circuit as shown in Unoperate...

Page 10: ...in Unoperated condition Terminals 1 4 M S 1 and 5 8 M S 2 open Terminals 1 3 M S 1 and 5 7 M S 2 closed N C N O COM N C 1 2 3 4 5 6 M S 1 M S 2 7 8 N O COM EOL 4B Circuit as shown in Operated conditi...

Page 11: ...S 1 M S 2 R B Y R B Y R B Y R B Y 5B Circuit as shown in Operated condition Terminals 1 2 M S 1 and 4 5 M S 2 open Terminals 1 3 M S 1 and 4 6 M S 2 closed R N POTTS Optional Single or Double Microswi...

Page 12: ...uipment II 2G Ex d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Ele...

Page 13: ...d IIC T6 T5 Gb II 2D Ex tb IIIC T90 C T80 C Db Standards applied EN 60079 0 2018 EN 60079 1 2014 EN 60079 31 2014 IP6X Dust Protection to EN60079 0 EN60079 31 Directive 2014 30 EU Electromagnetic Comp...

Reviews: