Document No. D202-00-211-IS
Issue 4 16-12-2022 Sheet 1 of 7
1) WARNING:
USE COVER BOLTS CLASS A4-70
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
POTENTIAL ELECTROSTATIC HAZARD
FOR INDOOR OR OUTDOOR USE
TO REDUCE THE RISK OF IGNITION OF
HAZARDOUS ATMOSPHERES, CONDUIT
RUNS MUST HAVE A SEALING FITTING
CONNECTED WITHIN 18 INCHES OF
CONDUIT
CAUTION - RISK OF ELECTRIC SHOCK -
MORE THAN ONE DISCONNECT MAY BE
REQUIREDTO DE-ENERGIZE THE
EQUIPMENT BEFORE SERVICING
AVERTISSEMENT:
UTILISER COUVRIR BOULONS CLASSE A4-
70
NE PAS OUVRIR UN PRESENCE
D'ATMOSPHERE EXPLOSIVE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - VOIR LES
INSTRUCTIONS
POUR USAGE INTÉRIEUR OU EXTERIEUR
POUR RÉDUIRE LE RISQUE
D'INFLAMMATION DES ATMOSPHÈRES
DANGEREUSES, LES CONDUITES DE
CONDUIT DOIVENT AVOIR UN RACCORD
D'ÉTANCHÉITÉ RACCORDÉ À MOINS DE 18
POUCES DE L'ENFERMEMENT
ATTENTION - RISQUE DE CHOC
ELECTRIQUE - PLUSIEURS SECTIONNEURS
PEUVENT ETRE NECESSAIRES POUR
COUPER L'ALIMENTATION DE
L'APPAREILLAGE AVANT
D'ENTREPRENDRE L'ENTRETIEN
2) Rating & Marking Information
2.1 NEC & CEC Class / Division Ratings for US / Canada
The GNExCP7 callpoints comply with the following
standards:
UL 60947-4-1 Low voltage switchgear and controlgear – Part 4-1:
Contactors and motorstarters – Electromechanical contactors and
motorstarters – Ed. 3 Rev. date 2017/10/
CSA C22.2 NO. 60947-4-1-14 Low voltage switchgear and
controlgear – Part 4-1: Contactors and motorstarters –
Electromechanical contactors and motorstarters – Ed. 2 - Issue Date
2014/01/04
The GNExCP7 callpoints are rated as follows:
Class I Div 2 Group ABCD T6 Ta -55°C to +60°C
Class II Div 2 Group FG T4 Ta -55°C to +60°C
Class III Div 1 & 2 Ta -55°C
to +60°C
2.2 NEC Class / Zone ratings US
The GNExCP7 callpoints comply with the following
standards:
UL 60079-0:2017 (Ed 6): Explosive Atmospheres - Part 0: Equipment
- General requirements
UL 60079-1:2015 (Ed7): Explosive Atmospheres - Part 1: Equipment
protection by flameproof enclosures “d”
UL 60079-31:2012 (Ed 2): Explosive Atmospheres - Part 31:
Equipment dust ignition protection by enclosure "t"
The GNExCP7 callpoints are rated as follows:
Class I Zone 1 AEx db IIC T6 Gb (Ta -55°C to +60°C)
Zone 21 AEx tb IIIC T125°C Db (Ta -55°C to +60°C)
2.3 CEC Class / Zone ratings Canada
The GNExCP7 callpoints comply with the following
standards:
CSA C22.2 NO. 60079-0:2015 (Ed 3) Explosive Atmospheres – Part
0: Equipment – General requirements
CSA C22.2 NO. 60079-1:2016 (Ed 3): Explosive Atmospheres – Part
1: Equipment protection by flameproof enclosures “d”
CSA C22.2 NO. 60079-31:2015 (Ed 2): Explosive Atmospheres –
Part 31: Equipment dust ignition protection by enclosure “t”
The GNExCP7 callpoints are rated as follows:
Class I Zone 1 Ex db IIC T6 Gb X (Ta -55°C to +60°C)
Zone 21 Ex tb IIIC T125°C Db (Ta -55°C to +60°C)
2.4 ATEX / IECEx / UKEX Certification
The GNExCP7 callpoints comply with the following
standards:
EN60079-0:2018 / IEC60079-0:2017 (Ed 7): Explosive Atmospheres
– Part 0: Equipment. General requirements
EN60079-1:2014 / IEC60079-1:2014 (Ed 7): Explosive Atmospheres
- Part 1: Equipment protection by flameproof enclosures "d"
EN 60079-31:2014 / IEC 60079-31:2013 (Ed 2): Explosive
Atmospheres - Part 31: Equipment dust ignition protection by
enclosure "t"
INSTRUCTION MANUAL
GNExCP7-PB-S, GNExCP7-PB-D, GNExCP7-PM-S, GNExCP7-PM-D,
GNExCP7-PT-S & GNExCP7-PT-D CALL POINTS
For use in Flammable Gas Atmospheres