General Installation Manual
Module Specifications
• Module specifications are shown in Table 1, 2 and Figure 1, 2, 3. (Electrical specifications, mechanical specifications,
module dimensions)
• Under real conditions, a photovoltaic module may experience conditions that produce more current and/or voltage
than reported at Standard Test Conditions. Therefore, the Isc value of modules should be multiplied by a factor of 1.25
to determine ampacity. An additional factor of 1.25 may be required for sizing conductors, fuses, disconnects, etc.
Please refer to
section 690.8 of the National Electric Code (NEC)
for guidelines. The Voc must be factored according to
the lowest recorded ambient temperature recorded for the location where the modules will be installed. Please refer
to
section 690.7 of the NEC
for more information regarding voltage temperature factors.