Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
82
Action
Data, etc.
which will be
deleted
Data, etc.
which will be
not deleted
Restart
code
Power down
(de-energize)
40
and
then
power up
again. ("Cold restart")
SSW
FFD, WASV
SSD,
S/W
00
Via menu H8/S6
Safe shut down of
control unit. ("Cold restart")
FFD, WASV
SSD,
S/W, SSW
00 alt. 03
Via
RESET
button on Main board
and MMI board respectively.
41
FFD, WASV
SSD,
S/W, SSW
42
Reset
command via WinG3 or
TLON Manager.
FFD, WASV
SSD,
S/W, SSW
42
Automatically
after download of site
specific data (SSD) via a PC &
WinG3. ("
Warm restart
")
FFD, WASV
SSD,
S/W, SSW
03
Automatically
after download of
S/W and text file via a PC & WinG3.
("Cold restart")
FFD, WASV
SSD,
S/W
43
, SSW
00 alt. 03
Automatically
due to external
disturbance.
44
("Cold restart")
FFD, WASV
SSD,
S/W, SSW
45
01, 02 alt.
04-20
NOTE!
During the restart, the fault output (relay) for the Fault tx will
be "activated", the supervised 24 V DC outputs S0-S3 will be not
supervised and S0-S3 programmed as normally high will be low for a
few seconds.
During the "restart", no fire alarm can be activated and the following
is show in the display:
Panasonic
40
Both rectifier (mains) and battery disconnected.
41
First press the
RESET
button on Main board momentarily then the
RESET
button on MMI board momentarily.
42
If in the middle of a process, also the SSW might be deleted.
43
The old S/W and text file will be deleted.
44
If this happens, call for service personnel / engineer.
45
Depending on the restart reason, also the SSW might be deleted.