Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
105
27
Present system status (H4)
If printer 5058 - an option for control unit 5000 – is mounted, it is
possible to get a print-out from some of the menus. In this case, the
soft key "Print" (P5) shall be used.
NOTE!
During printing "Print"
will be replaced with "Abort printing".
27.1
Disablement (H4/U1)
This is a dynamic list of all disablements in the system. Also alarm
point(s) and/or zones disabled via "Single reset with automatic
disablement" (see page 50) are shown in the list. In this case a
zone
will be displayed as ZZZ-00 (i.e. a zone number and address 00).
Disablements by time channels are listed in menu H4/U2.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H4.
H4 Present system status
"
↵
"
U1 Disablement
U2 Disablement by time channel
U3 Open doors
U4 Sensor values
U5 Sensors activating SERVICE signal
U6 Event log
U7 Information
Press "
↵
" to show all
disablements in the system
(U1).
"
↵
"
(When "
↵
" is pressed, the disablements will be shown in the
display. Some examples:)
Zone XXX address XX disabled
yyyy-mm-dd hh:mm
Zone XXX is disabled
yyyy-mm-dd hh:mm Automatic re-enabl
Alarm points are disabled by time channel in CU XX
yyyy-mm-dd hh:mm
....
D
isablement 1 to 3 of 7
Escape
menu
A dynamic list in which
you can scroll with "▼" or
"▲".
If printer is mounted the
soft key "Print" will be
visible, else not. Press
"Print" for a print-out of all
items in the list.
If there are no
disablements when "
↵
" is
pressed, the list view will
not open.
"ESC"
U1 Disablement
Scroll to another menu or
press "
ESC
".