Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
104
26
Set calendar and clock (H3)
The RTC component has a capacitor as a backup power supply.
Normally, date, day of the week and time only have to be set when the
power is turned on the control unit for the first time.
50
If required, the
clock might be corrected, so that the "time stamps" for fire alarms,
faults, etc. will be correct.
The calendar and clock can be set in any c.i.e. for the whole system.
Every day (at midnight) the calendar and clock will be synchronised.
NOTE! If you don't want to change anything, press "ESC"
instead of "
↵
" to return to menu H3.
Action
Text in display
Comments
"Menu"
According to chapter
"Access", see page 85.
Scroll to menu H3.
H3 Set calendar and clock
"
↵
"
YY
Y
Y-MM-DD hh:mm
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
The date & time shown
was valid when this menu
was opened. When
required, change the date,
time and/or weekday
(press "▼" or "▲" to
select the weekday).
The "clock" starts again as
from the date, time, etc.
shown in the display
when
you press "
↵
".
If no
changes shall be done,
press "ESC" instead of
"
↵
".
"
↵
"
H3 Set calendar and clock
Scroll to another menu or
press "ESC".
NOTE!
When the Russian, Ukraine, Australian or the New Zealand language
is selected the date is shown as follows:
DD-MM-YYYY
.
50
The capacitor can supply the RTC for a couple of days. When the power
has been turned off, it is recommended to check / set the date and time in
menu H3.