Operating Instructions Fire alarm system EBL512 G3, V1.1.x
69
17.2
Fault acknowledge
The LEDs
Routing equipment
"Fault tx activated" (L13) and
Fault /
Disablements
"General fault" (L9) are turned on
30
.
(LEDs
Fault / Disablements
"Alarm devices" (L11), "System fault"
(L7) and/or
Fault / Disablements
"Fire brigade tx" (L12) might be
turned on as well.
Output(s) for routing equipment (Fault tx) is (are) activated.
Output(s) for general fault is (are) activated.
Output(s) for general charge fault might be activated.
One or more fault messages incl. date and time are shown in the
control unit display.
If
Fault latching
is selected in WinG3 (default), after the time might
be shown
"
serviced
"
= the fault is already serviced / corrected.
Example: Fault messages shown in the control unit display:
FAULT: No reply zone: 123 address: 01
technical
number 000025
2009-10-02 15:22 serviced
FAULT: No reply zone: 123 address: 03
technical number 000027
2009-10-06 09:25
FAULT: No reply zone: 234 address: 01
technical number 002112
2009-11-06 15:25
Number of not ackn. faults in system: 5
Extinguishing fault Extinguishing wire fault
31
Login, according to chapter "Access", page 85.
Use
menu H6
(access level 2B) for fault acknowledge, see
chapter "FAULT Acknowledge (H6)", page 126. Menu H6
is a list showing a maximum of 200 faults (not acknow-
ledged faults and/or acknowledged but not serviced /
corrected faults).
30
Indicating that output for routing equipment (Fault tx) is activated.
31
If one of the faults is
FAULT: Extinguishing system, control
unit xx
, also the information text
Extinguishing fault
will shown.
If one of the faults is
FAULT: Supervised output x, control unit
xx
and the output type is "Extinguishing", also the information text
Extinguishing wire fault
will shown. The information text is shown
also during a fire alarm.