Panasonic Electric Works Nordic AB
MEW01349
Rev: -
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
110
27.4.1
Reset of a week average sensor value
If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
cleared, i.e. set to the default value. If not, the new / clean sensor will
inherit the old sensor's value. It is possible to clear the week average
sensor value for each sensor individually, see chapter "Clear weekly
average (H8/S4)", page 134. See also chapter "Acknowledge
SERVICE signal (H8/S3)", page 132.
NOTE!
Authorised service personnel only, must do the reset to
default value. Used incorrectly it can cause nuisance fire alarms.