11.4. Outdoor Unit
11.4.1.
INSTALL THE OUTDOOR UNIT
• After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and
horizontally by bolt nut (ø10 mm).
2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly
with bolt or nails.
11.4.2.
CONNECTING THE PIPING
Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe
(in case of using long piping).
Connect the piping
• Align the center of piping and sufficiently tighten the flare nut with fingers.
• Further tighten the flare nut with torque wrench in specified torque as stated in the table.
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut
(locate at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder entering the pipe.
3. Please make flare after inserting the flare nut onto the copper pipes.
Model
Piping size (Torque)
Gas
Liquid
YW9GK, YW12GK
3/8” [42 N
O
m]
1/4” [18 N
O
m)
Summary of Contents for CS-YW9GKE
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS YW9GK CS YW12GK...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU YW9GK CU YW12GK...
Page 12: ...12 6 Refrigeration Cycle Diagram...
Page 13: ...13 7 Block Diagram...
Page 15: ...15 9 Electronic Circuit Diagram...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board...
Page 17: ...17 10 2 Indoor Unit Power Printed Circuit Board...
Page 18: ...18 10 3 Indicator TOP VIEW BOTTOM VIEW...
Page 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Page 33: ...33 Normal Deicing Time Diagram Overload Deicing Time Diagram...
Page 43: ...43...
Page 44: ...44 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
Page 45: ...45...
Page 46: ...46 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry Heating...
Page 48: ...48 16 3 Operation Characteristics 16 3 1 CS YW9GK CU YW9GK...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52 16 3 2 CS YW12GK CU YW12GK...
Page 53: ...53...
Page 54: ...54...
Page 55: ...55...