30
12.5.5.
Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5
°
C (cooling mode) or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
V
T = Intake air temperature - Indoor heat exchanger temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
12.5.6.
Starting Current Control
• When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to
operate at 1.6 second later.
• The reason of the difference is to reduce the starting current flow.
12.5.7.
Dew Prevention Control
• Purpose is to prevent dew formation on indoor unit air discharge area.
• When room temperature is constant (±1
°
C) the following conditions occur for 30 minutes continuously, anti-dew formation will
activate:
- Remote Control setting temperature is less than 25
°
C.
- Compressor is on.
- Cooling operation mode.
- Indoor fan motor operate at Low fan speed (CLo, Lo- or QLo).
• This control is cancelled immediately when above condition is changed, or Powerful button is pressed.
• Anti-Dew formation is control by:
1. CLo fan is changed to HLo fan.
(For 12.5.8 to 12.5.16 information applies only to Heating Operation)
12.5.8.
Restart Control (Time Delay Safety Control)
• When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
- Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
• This phenomenon is to balance the pressure inside the refrigerant cycle.
12.5.9.
Compressor Reverse Rotation Protection Control
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between indoor heat
exchanger and intake air is 5°C (heating mode) or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
V
T = Indoor heat exchanger temperature - Intake air temperature
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
Summary of Contents for CS-YW9GKE
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS YW9GK CS YW12GK...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU YW9GK CU YW12GK...
Page 12: ...12 6 Refrigeration Cycle Diagram...
Page 13: ...13 7 Block Diagram...
Page 15: ...15 9 Electronic Circuit Diagram...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board...
Page 17: ...17 10 2 Indoor Unit Power Printed Circuit Board...
Page 18: ...18 10 3 Indicator TOP VIEW BOTTOM VIEW...
Page 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Page 33: ...33 Normal Deicing Time Diagram Overload Deicing Time Diagram...
Page 43: ...43...
Page 44: ...44 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
Page 45: ...45...
Page 46: ...46 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry Heating...
Page 48: ...48 16 3 Operation Characteristics 16 3 1 CS YW9GK CU YW9GK...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52 16 3 2 CS YW12GK CU YW12GK...
Page 53: ...53...
Page 54: ...54...
Page 55: ...55...