20
11.3. Indoor Unit
11.3.1.
HOW TO FIX INSTALLATION PLATE
The mounting wall is strong and solid enough to prevent it from
the vibration.
The centre of installation plate should be at more than 450 mm
at right and left of the wall.
The distance from installation plate edge to ceiling should more
than 67 mm.
From installation plate left edge to unit’s left side is 74 mm.
From installation plate right edge to unit’s right is 94 mm.
1. Mount the installation plate on the wall with 5 screws or
more.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
• Always mount the installation plate horizontally by
aligning the marking-off line with the thread and using a
level gauge.
2. Drill the piping plate hole with ø70 mm hole-core drill.
• Line according to the left and right side of the installation
plate. The meeting point of the extended line is the
centre of the hole. Another method is by putting
measuring tape at position as shown in the diagram
above. The hole centre is obtained by measuring the
distance namely 150 mm and 125 mm for left and right
hole respectively.
• Drill the piping hole at either the right or the left and the
hole should be slightly slanted to the outdoor side.
11.3.2.
TO DRILL A HOLE IN THE WALL
AND INSTALL A SLEEVE OF
PIPING
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm from the
wall.
4. Finish by sealing the sleeve with putty or caulking
compound at the final stage.
11.3.3.
INDOOR UNIT INSTALLATION
1. For the right rear piping
2. For the right and right bottom piping
: For left side piping, piping connection for liquid should be about
15 mm from this line.
: For left side piping, piping connection for gas should be about
45 mm from this line.
: For left side piping, piping connection cable should be about
800 mm from this line.
Caution
When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
Summary of Contents for CS-YW9GKE
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS YW9GK CS YW12GK...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU YW9GK CU YW12GK...
Page 12: ...12 6 Refrigeration Cycle Diagram...
Page 13: ...13 7 Block Diagram...
Page 15: ...15 9 Electronic Circuit Diagram...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board...
Page 17: ...17 10 2 Indoor Unit Power Printed Circuit Board...
Page 18: ...18 10 3 Indicator TOP VIEW BOTTOM VIEW...
Page 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Page 33: ...33 Normal Deicing Time Diagram Overload Deicing Time Diagram...
Page 43: ...43...
Page 44: ...44 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
Page 45: ...45...
Page 46: ...46 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry Heating...
Page 48: ...48 16 3 Operation Characteristics 16 3 1 CS YW9GK CU YW9GK...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52 16 3 2 CS YW12GK CU YW12GK...
Page 53: ...53...
Page 54: ...54...
Page 55: ...55...