36
12.7. Outdoor Fan Speed Control
• There is only one speed for outdoor fan motor.
• When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously.
• Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.
12.8. Vertical Airflow Direction Control
12.8.1.
Auto Control
(Cooling and Soft Dry Operation condition)
• When the vertical airflow direction is set to Auto using the
remote control, the louver swings up and down as shown in
the diagram.
• When stop operation using the remote control, the discharge
vent is reset, and stop at the closing position.
• During Cooling operation or Soft Dry operation, indoor fan
motor may stop to rotate at certain periods. At that condition,
the louver will stop swinging and rest at the upper limit.
• During Anti-dew condensation prevention, Airflow Direction
Auto-control angle change from 0
°
-32
°
to 20
°
-30
°
under
Cooling and Soft Dry operation mode.
(Heating Operation condition)
• When the piping air temperature reaches 38°C, the louver is
changed from upper to lower limit. When the piping air
temperature falls to 35°C, the louver is changed from lower
to upper limit.
Cooling and Soft Dry Operation
Heating Operation
12.8.2.
Manual Control
• When the vertical airflow direction is set to Manual using the remote control, the automatic airflow is released and the airflow
direction louver move up and down in the range shown in the diagram.
• The louver can be adjusted by pressing the button to the desired louver position.
• When stop operation using the remote control, the discharge vent is reset, and stop at the closing position.
• During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 10
°
, 15
°
, 20
°
, 26
°
, 32
°
to 22
°
, 24
°
,
26
°
, 28
°
, 30
°
under Cooling and Soft Dry operation mode.
Cooling and Soft Dry Operation
Heating Operation
Summary of Contents for CS-YW9GKE
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS YW9GK CS YW12GK...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU YW9GK CU YW12GK...
Page 12: ...12 6 Refrigeration Cycle Diagram...
Page 13: ...13 7 Block Diagram...
Page 15: ...15 9 Electronic Circuit Diagram...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board...
Page 17: ...17 10 2 Indoor Unit Power Printed Circuit Board...
Page 18: ...18 10 3 Indicator TOP VIEW BOTTOM VIEW...
Page 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Page 33: ...33 Normal Deicing Time Diagram Overload Deicing Time Diagram...
Page 43: ...43...
Page 44: ...44 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
Page 45: ...45...
Page 46: ...46 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry Heating...
Page 48: ...48 16 3 Operation Characteristics 16 3 1 CS YW9GK CU YW9GK...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52 16 3 2 CS YW12GK CU YW12GK...
Page 53: ...53...
Page 54: ...54...
Page 55: ...55...