12.5.10. 30 Minutes Time Save Control
• The compressor will start automatically if it has stopped for 30 minutes and the intake air temperature falls between the
compressor OFF temperature (A) and compressor ON temperature (B) during the period.
• This is maintain the room temperature as set. Despite of this, it is to prevent a wrong judgement of intake air temperature due to
poor installation near the sensor area.
12.5.11. Overload Protection Control
• Outdoor Fan Control
- If the temperature of the indoor heat exchanger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor
heat exchanger temperature falls to 49°C.
• Compressor high pressure protection
- If the indoor heat exchanger becomes 65° C or more, the compressor will stop and restart automatically.
(Time Delay Safety Control - 4 minutes waiting).
- This is to reduce the pressure, as to reduce the indoor heat exchanger temp. Nevertheless, is to protect the compressor from
overload of too high temperature.
12.5.12. 4-Way Valve Control
• 4-way valve always on during Heating operation. (except deicing operation)
• When the unit is switched off by remote control during Heating operation, the 4-way valve stay at Heating position for 5 minutes.
• This is to prevent the refrigerant flow process sound for being occur.
12.5.13. Outdoor Fan Motor Control
• When compressor stops (reaches room temperature), outdoor fan will operate for 30 seconds (forced operation).
• This is to release the heat and to obtain the lowest pressure as fast as possible.
12.5.14. Hot Start Control
• Hot Start Control is to prevent cool air discharge into the room when heating operation start.
• When Heating operation starts, Indoor fan will not start until the indoor heat exchanger reaches 30°C as diagram shown.
• Hot start is completed when indoor heat exchanger rises to 39°C or operation over 4 minutes.
Summary of Contents for CS-YW9GKE
Page 10: ...10 5 Dimensions 5 1 Indoor Unit Remote Control 5 1 1 CS YW9GK CS YW12GK...
Page 11: ...11 5 2 Outdoor Unit 5 2 1 CU YW9GK CU YW12GK...
Page 12: ...12 6 Refrigeration Cycle Diagram...
Page 13: ...13 7 Block Diagram...
Page 15: ...15 9 Electronic Circuit Diagram...
Page 16: ...16 10 Printed Circuit Board 10 1 Indoor Unit Main Printed Circuit Board...
Page 17: ...17 10 2 Indoor Unit Power Printed Circuit Board...
Page 18: ...18 10 3 Indicator TOP VIEW BOTTOM VIEW...
Page 21: ...21 3 For the embedded piping This can be used for left rear piping and left bottom piping also...
Page 33: ...33 Normal Deicing Time Diagram Overload Deicing Time Diagram...
Page 43: ...43...
Page 44: ...44 15 2 Indoor Fan Motor and Cross Flow Fan Removal Procedures...
Page 45: ...45...
Page 46: ...46 16 Technical Data 16 1 Thermostat Characteristics Cooling Soft Dry Heating...
Page 48: ...48 16 3 Operation Characteristics 16 3 1 CS YW9GK CU YW9GK...
Page 49: ...49...
Page 50: ...50...
Page 51: ...51...
Page 52: ...52 16 3 2 CS YW12GK CU YW12GK...
Page 53: ...53...
Page 54: ...54...
Page 55: ...55...