9.2.2. 2-2 Balance refrigerant of the 2-way, 3-way valves
(Gas leakage)
Procedure
1. Confirm that both 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the service port of the 3-way valve.
•
•
•
•
Leave the valve on the charge set closed.
•
•
•
•
Connect the charge hose with the push pin to the service port.
3. Open the valves (low side) on the charge set and discharge the refrigerant until the gauge indicates 0.5-1 kg/cm
2
G (0.05-
0.1Mpa).
•
•
•
•
If there is no air in the refrigerant cycle [the pressure when the air conditioner is not running is higher than 1kg/cm
2
G
(0.1Mpa)], discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm
2
G (0.05 to 0.1Mpa). If this is the case, it will not
be necessary to apply a evacuation.
•
•
•
•
Discharge the refrigerant gradually, if it is discharged too suddenly, the refrigerant oil will also be discharged.
44
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Summary of Contents for CS-SA9CKP
Page 9: ...3 Dimensions 9 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 10: ...10 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 11: ...4 Refrigeration Cycle Diagram 11 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 12: ...5 Block Diagram 12 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 13: ...6 Wiring Diagram 13 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 17: ...Time Graph for soft dry operation 17 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 26: ...26 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 55: ...13 Exploded View CS SA9CKP CS SA12CKP 55 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 57: ...15 Exploded View CU SA9CKP5 CU SA12CKP5 57 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...
Page 61: ...17 1 REMOTE CONTROL 61 CS SA9CKP CU SA9CKP5 CS SA12CKP CU SA12CKP5...