67
14.5.13 H98 (Indoor High Pressure Protection)
Error Code will not display (no Timer LED blinking) but store in EEPROM
Malfunction Decision Conditions
During heating operation, the temperature detected by the indoor pipe temperature sensor is above 60°C.
Malfunction Caused
Air short circuit.
Clogged air filter of the indoor unit.
Dust accumulation on the indoor unit heat exchanger.
2/3 way valve closed.
Detection error due to faulty indoor fan motor.
Excessive
refrigerant.
Clogged expansion valve or strainer.
Detection error due to faulty indoor pipe temperature sensor.
Detection error due to faulty indoor unit PCB.
Troubleshooting